To Test the CCI, connect the leads together and check 
the LED response. 

If  the phases are correctly 
connected at both A & B 
Then phase identification at C is 
valid  using a receiver at either 
(not both)  A and B. 
 
If the phasing  is correct at A but 
incorrect at  B then you will not be 
able to correctly identify phases 
at C. 
 
If you disconnect at B using a 
receiving at  A  identification of 
correct phasing is possible at 
both B and C. 

 

USING THE BOWDEN BROS CABLE CORE IDENTIFIER  

ON A TEE CONNECTED CIRCUIT.

 

  

 

Summary of Contents for Cable Core Identifier

Page 1: ...tifier is designed as a simple tool to correctly identify the phase rotation of a three phase cable at a remote point on a known cable Follow these simple instructions for operation WARNING 1 Do not connect the CCI to a cable that has not been fully discharged Damage WILL be caused and is not covered under our warranty 2 Only use an Industrial Alkaline PP3 battery of the type supplied with the ins...

Page 2: ...tery cover and battery Remove battery terminal cover and connect PP9 battery Replace battery cover Push button on transmitter to carry out battery test If GREEN LED does not light change the battery but only with an industrial capacity Alkaline PP3 Connect the receiver leads to the switchgear prods or the connected cable end If the colours do not match make a note of the relationship between the l...

Page 3: ...itter In this example the RED LED is ON The Yellow LED is OFF The GREEN LED always lights Now follow the instructions on the back of the Transmitter The instructions have told us to swap the YELLOW and BLUE leads Press the button again and the RED LED is OFF the YELLOW LED is ON Refer to the instructions again The instructions tell us to swap the RED and BLUE leads Press the button and both the RE...

Page 4: ... both A B Then phase identification at C is valid using a receiver at either not both A and B If the phasing is correct at A but incorrect at B then you will not be able to correctly identify phases at C If you disconnect at B using a receiving at A identification of correct phasing is possible at both B and C A B C USING THE BOWDEN BROS CABLE CORE IDENTIFIER ON A TEE CONNECTED CIRCUIT ...

Reviews: