1. General Information
Please note that the following installation conditions must be obeyed:
Pressure Requirement: PN16/PS16.
Environmental Class: E1, M1, A
Installation requirement: There must be a distance of minimum 25 cm between signal
cables and other installations
If medium temperature is below 10
°
C or above 90
°
C in flow sensor, It
’
s recommended
that the calculator be wall-mounted.
Note: Seal or any safety marks on the meter must not be damaged or removed, and doing so
will void the warranty and calibration of the meter.
Key Information:
Flow Sensor
Registers the amount of district heating water in m³/h circulating
through the heating system.
Θ: 3°C~95°C
Temperature Sensors
Placed in forward and return pipes sense the cooling, by the
difference between in flow and out flow temperatures.
Θ: 0°C~105°C
Calculator
Calculates heat energy consumption based on flow volume and
temperature loss of heating water.
Θ: 3°C~95°C
△
Θ: 4K~65K
Electromagnetic environment
E1 (housing/light industry). The meter’s control cables must be
drawn at min. 25 cm distance to other installations.
Mechanical environment
M1 (fixed installation with minimum vibration).
Climatic environment
The meter
must
be
installed
in
environments
with
non-condensing humidity as well as in closed locations
(indoors). The ambient temperature must be within 5~55°C.
Maintenance and repair
The district heating supplier can replace temperature sensor
and battery. The flow sensor must not be separated from the
calculator.
B12 VI Series must be connected to a temperature sensor pair
type Pt1000.
Battery for replacement
B12 VI Series can be fitted with ER18505 or ER26500 with
operating time of 6/11 years replaceable.