33598-6-0115
Page 19
VENT CAP
9” (229 mm)
MINIMUM TO SIDE WALL
Figure 27
VENTING FIREPLACE
10”
(254mm)
12”
(305mm)
A
CENTER OF FRAMING
(MINIMUM VENT)
V
CENTER
OF ELBOW
H
C
B
C
B
Figure 26
MINIMUM HOLE LOCATION DIMENSIONS FOR THROUGH THE
WALL HORIZONTAL INSTALLATIONS WITH 90 DEGREE ELBOW
OFF TOP OF FIREPLACE
Positioning the Fireplace
FIREPLACE
SERIES
HARD ELBOW DIMENSIONS
A
B
C
DVLL/DVTL
55-5/8 in.
(141.3 cm)
5 in.
(127 mm)
7 in.
(178 mm)
Determine the exact position of the appliance so the direct vent
termination will be centered (if possible) between two (2) studs. This
will avoid any extra framing. All vent kit pipes should be assembled
on the unit after the unit is moved into the final position.
Cutting the Hole
After the fireplace has been positioned in its permanent location,
the hole through the exterior wall of the house can be cut. This hole
must be 12 in. (305mm) high x 10 in. (254mm) wide with its center
line determined by the amount of vertical rise and horizontal run of
the termination.
See Figure 26.
When locating the hole it must be
noted that the bottom of the cap must be 12 in. (305mm) above the
ground level, and top of the cap must be no less than 18 in. (457mm)
below a combustible projection, and no closer than 9 in. (229mm)
to any wall running parallel to vent termination.
See Figure 27.