Boston gear Ratiotrol P-3026-BG Installation And Operation Manual Download Page 7

7

P-3026 • Doc. No. 60881 • Boston Gear

®

Ratiotrol

®

DC Motor Speed Control

Installation

AC Power Connections

Connect the AC input power wires to controller

Terminals L1 and L2 on Terminal Board TB1.

(

See Figure 5

)

If one of the power wires is a neutral wire

(grounded potential), connect the hot wire (H) to

Terminal L1 and the neutral wire (N) to Terminal

L2. Connect the controller Ground Screw

(GND) to an earth ground according to

applicable electrical codes. Ground Screw

(GND) is located near the bottom of the

controller enclosure. (

See Figure 5

)

If the neutral wire (Terminal

L2) is not grounded, the

controller remains electrically "hot" when the

AC power ON/OFF switch is turned off.

Motor Connections

Check the connection diagram supplied on or

with the motor. If the motor has dual voltage

shunt fields, connect the field terminal straps (or

leads) for low field voltage.

Connect the motor field and armature terminals

(or leads) to controller Terminals F+, F-, A+, and

A-, respectively, on Terminal Board TB1.

Do not ground the motor

wiring. Grounded wiring can

cause controller damage.

Connect the motor thermal guard, if applicable,

to Terminals 2 and 3 on Terminal Board TB2.

Be sure to remove the jumper wire from

Terminals 2 and 3 if a thermal overload is used.

(

See Figure 5

)

Initial Startup

Before energizing the controller for the first

time, be familiar with any installed options.

See the option selection table on the controller

data label.

The controller has been factory tested and

adjusted with a motor under simulated

operating conditions. Therefore, startup

adjustments should not be needed. However,

the following startup procedure should be

performed for proper operation, system

compatibility, and safety.

1. Be sure all interconnection wiring is correct,

and all wiring terminations are tightened

securely. Wiring errors and accidental

grounds can cause controller and/or

motor damage.

2. For 50 Hertz operation, be sure the 60 Hz

jumper wire is removed (cut out) from the

control board. (

See Figure 5

)

3. Close and latch the enclosure cover.

4. Turn the MOTOR SPEED potentiometer fully

counterclockwise to zero.

5. If so equipped, place the RUN/JOG switch in

RUN position and the FWD/REV switch in

FWD position.

6. Couple the motor to the machine (load).

7. Turn on the AC input power and the AC

POWER ON/OFF switch.

8. Depress the RUN button, and slowly turn the

MOTOR SPEED potentiometer clockwise

until the motor rotates. If motor rotation is

opposite to that desired, stop the motor with

the STOP button, turn off the AC POWER

ON/OFF switch and the AC input power, and

interchange the motor armature leads.

Never use line switching to

start and stop the motor.

Resulting transients may cause controller

damage.

9. Turn the MOTOR SPEED potentiometer fully

clockwise to 100 and observe motor rotation.

The motor should run at its rated (base)

speed.

10. Turn the MOTOR SPEED potentiometer

fully counterclockwise to zero and depress

the STOP button.

Section II

CAUTION

CAUTION

WARNING

Summary of Contents for Ratiotrol P-3026-BG

Page 1: ...Boston Gear Ratiotrol DC Motor Speed Control Doc No 60881 VEL Series 1 6 1 HP VEH Series 1 3 HP Installation and Operation P 3026 BG An Altra Industrial Motion Company...

Page 2: ...Controller 9 Section IV Maintenance 10 General 10 Adjustment Instructions 10 Troubleshooting 12 Section V Parts List 15 Section VI Options 16 Section VII Illustrations 17 List of Illustrations Figure...

Page 3: ...AC VEL16 1 6 HP VEL25 1 4 HP VEL33 1 3 HP VEL50 1 2 HP VEL75 3 4 HP VEL100 1 HP 2 VEH100 VEH500 230VAC VEH100 1 HP VEH150 1 1 2 HP VEH200 2 HP VEH300 3 HP Basic Units Standard VEL and VEH Controllers...

Page 4: ...should not exceed 55 degrees C Performance Characteristics 1 Speed Range controlled 0 to motor base speed 2 Speed Range At Rated Torque and Regulation 30 1 3 Efficiency maximum speed a Controller SCR...

Page 5: ...when the motor armature current exceeds 120 for 80 seconds An optional current load monitor Option Kit Cat No 60177 is available which provides an adjustable trip range and an adjustable time delay r...

Page 6: ...ents and surges However to prevent problems from high energy transients and large surges observe the following 1 Place the controller on a feeder line separate from that supplying large inductive load...

Page 7: ...on selection table on the controller data label The controller has been factory tested and adjusted with a motor under simulated operating conditions Therefore startup adjustments should not be needed...

Page 8: ...s the RUN button and the motor will accelerate to the setting of the MOTOR SPEED potentiometer Stop To stop the motor depress the STOP button and the motor will stop at a rate proportional to the moto...

Page 9: ...interlock which requires a momentary relaxation of pressure before the reverse position can be engaged This center position causes a Stop function and an antiplug circuit prevents the motor from bein...

Page 10: ...d result stop the motor turn off the AC input power and refer to the Troubleshooting Table Table 5 Refer to Figure 4 for the location of the internal adjustment potentiometers Preliminary 1 Be sure th...

Page 11: ...and 6 until desired speed regulation is attained Current Limit The current limit prevents excessive armature current and resulting excessive line current by limiting armature current at 150 of rated S...

Page 12: ...wiring terminating trips immediately when in the controller Correct accordingly turned on Circuit component or wiring grounded Remove unwanted ground Power Bridge BR1 shorted Replace BR1 Power board f...

Page 13: ...d Check shunt field current Insufficient shunt field current causes excessive armature current If field current is OK check for mechanical overload If unloaded motor shaft does not rotate freely repla...

Page 14: ...uses excessive armature current If field current is OK check for mechanical overload If unloaded motor shaft does not rotate freely replace motor bearings Also check for shorted armature Correct accor...

Page 15: ...Motor Speed 60246 All 1 Allen Bradley 72A1G Pot Jog Speed 60246 Jog Option No 9 1 Allen Bradley 72A1G048D5024 Knob Pot 60245 All 1 Rogan RB672AML T1 Transformer 60259 All 1 Inelco P 1883 APR Relay An...

Page 16: ...aking R Reversing Selector Switch MR Reversing Auto magnetic 9 Jog Selector Switch B Input Options 14 Master Override Board 17 Adj Linear Accel Decel 22 Tach Follower 25 Ext MA Signal Isolated 33 Spee...

Page 17: ...trations Section VII Max Control Proj 65 1 35 Circuit Breaker Operator Panel Mounting Slot Width 25 8 59 9 34 12 00 1 33 1 20 1 75 6 00 10 55 6 30 25 9 06 16 81 Conduit Entrance 3 4 14 N P T 4 Places...

Page 18: ...5 1 75 6 00 1 20 Conduit Entrance 3 4 14 N P T 6 Places 25 00 Approx 9 34 3 75 Approx 9 34 1 33 8 59 1 35 8 Mounting Slots 25 Wide 9 06 16 81 10 55 Figure 2 Approximate Weights VEL Controls 30 Pounds...

Page 19: ...19 P 3026 Doc No 60881 Boston Gear Ratiotrol DC Motor Speed Control Illustrations Section VII Ratiotrol D C Systems Figure 3 VEL VEH Series...

Page 20: ...2 AC1 11 8 9 E3 E19 E20 VEL 50VDC Field VEH 100VDC Field F F CB1 30A RV1 L1 L2 115V 230V 115V 115V Blk Wht T1 Power Bd Blk Red Blk Wht 24V 20V 20V 2 1 5 4 3 K1 E10 E13 13 E11 E12 12 14 15 D1 D2 D4 D3...

Page 21: ...action for direct or consequential damages to property or person The foregoing limited warranty is expressly made in lieu of all other warranties whatsoever express implied and statutory and includin...

Reviews: