Boston gear Ratiotrol P-3026-BG Installation And Operation Manual Download Page 11

IR Compensation

IR compensation is factory adjusted and sealed

for 3% maximum speed change with a 95%

load change throughout the motor speed range.

Therefore, readjustment should not normally be

necessary. However, if the following facilities

are available, readjustment can be performed.

To adequately adjust IR compensation, an

adjustable load is required that can be applied

and removed while the motor is running. In

addition, a close reading tachometer is needed

to record speed changes. If these facilities are

unavailable, do not readjust IR compensation.

If, during this adjustment procedure, motor

speed becomes unstable or oscillates (hunts),

slowly turn IR COMP potentiometer (R9)

counterclockwise until the hunting stops.

1. Turn IR COMP potentiometer (R9) fully

counterclockwise.

2. Remove the load from the motor and

depress the RUN button.

3. Turn the MOTOR SPEED potentiometer until

the motor runs at the maximum speed of the

desired speed range, normally rated motor

base speed. Record motor speed.

4. Apply load to the motor until it draws rated

armature current. (See Table 1 for motor

current ratings.) Note the speed change.

5. Turn IR COMP potentiometer (R9) until the

motor returns to the speed recorded in

Step 3.

6. Remove the load and repeat Step 3.

7. Repeat Steps 4, 5 and 6 until desired speed

regulation is attained.

Current Limit

The current limit prevents excessive armature

current and resulting excessive line current by

limiting armature current at 150% of rated.

Since the current limit is factory adjusted and

sealed, readjustment should not be performed

unless an application requires a lower limit of

armature current, e.g., limiting torque or

accelerating high inertia loads.

1. Turn off the AC input power and connect a

DC ammeter, with a rating of at least twice

rated armature current, in series with the

armature. Observe correct polarity when

connecting the ammeter. (

See Table 1 for

motor current ratings

.)

2. Turn the CURRENT LIMIT potentiometer

(R12) fully counterclockwise.

3. Connect maximum load to the motor.

4. Turn on the AC input power and the AC

POWER ON/OFF switch.

5. Turn the MOTOR SPEED potentiometer fully

clockwise.

6. Depress the RUN button, and slowly turn

CURRENT LIMIT potentiometer clockwise

(R12) while the motor is accelerating until

the ammeter records the desired armature

current.

Do not turn potentiometer

(R12) past the factory setting in

the increase direction.

Resulting excessive current could damage the

controller and motor.

To obtain a particular percentage of rated

output torque, set the armature current at a

percentage of rated armature current; e.g., 50%

torque is obtained with 50% rated armature

current.

11

P-3026 • Doc. No. 60881 • Boston Gear

®

Ratiotrol

®

DC Motor Speed Control

Maintenance

Section IV

CAUTION

Summary of Contents for Ratiotrol P-3026-BG

Page 1: ...Boston Gear Ratiotrol DC Motor Speed Control Doc No 60881 VEL Series 1 6 1 HP VEH Series 1 3 HP Installation and Operation P 3026 BG An Altra Industrial Motion Company...

Page 2: ...Controller 9 Section IV Maintenance 10 General 10 Adjustment Instructions 10 Troubleshooting 12 Section V Parts List 15 Section VI Options 16 Section VII Illustrations 17 List of Illustrations Figure...

Page 3: ...AC VEL16 1 6 HP VEL25 1 4 HP VEL33 1 3 HP VEL50 1 2 HP VEL75 3 4 HP VEL100 1 HP 2 VEH100 VEH500 230VAC VEH100 1 HP VEH150 1 1 2 HP VEH200 2 HP VEH300 3 HP Basic Units Standard VEL and VEH Controllers...

Page 4: ...should not exceed 55 degrees C Performance Characteristics 1 Speed Range controlled 0 to motor base speed 2 Speed Range At Rated Torque and Regulation 30 1 3 Efficiency maximum speed a Controller SCR...

Page 5: ...when the motor armature current exceeds 120 for 80 seconds An optional current load monitor Option Kit Cat No 60177 is available which provides an adjustable trip range and an adjustable time delay r...

Page 6: ...ents and surges However to prevent problems from high energy transients and large surges observe the following 1 Place the controller on a feeder line separate from that supplying large inductive load...

Page 7: ...on selection table on the controller data label The controller has been factory tested and adjusted with a motor under simulated operating conditions Therefore startup adjustments should not be needed...

Page 8: ...s the RUN button and the motor will accelerate to the setting of the MOTOR SPEED potentiometer Stop To stop the motor depress the STOP button and the motor will stop at a rate proportional to the moto...

Page 9: ...interlock which requires a momentary relaxation of pressure before the reverse position can be engaged This center position causes a Stop function and an antiplug circuit prevents the motor from bein...

Page 10: ...d result stop the motor turn off the AC input power and refer to the Troubleshooting Table Table 5 Refer to Figure 4 for the location of the internal adjustment potentiometers Preliminary 1 Be sure th...

Page 11: ...and 6 until desired speed regulation is attained Current Limit The current limit prevents excessive armature current and resulting excessive line current by limiting armature current at 150 of rated S...

Page 12: ...wiring terminating trips immediately when in the controller Correct accordingly turned on Circuit component or wiring grounded Remove unwanted ground Power Bridge BR1 shorted Replace BR1 Power board f...

Page 13: ...d Check shunt field current Insufficient shunt field current causes excessive armature current If field current is OK check for mechanical overload If unloaded motor shaft does not rotate freely repla...

Page 14: ...uses excessive armature current If field current is OK check for mechanical overload If unloaded motor shaft does not rotate freely replace motor bearings Also check for shorted armature Correct accor...

Page 15: ...Motor Speed 60246 All 1 Allen Bradley 72A1G Pot Jog Speed 60246 Jog Option No 9 1 Allen Bradley 72A1G048D5024 Knob Pot 60245 All 1 Rogan RB672AML T1 Transformer 60259 All 1 Inelco P 1883 APR Relay An...

Page 16: ...aking R Reversing Selector Switch MR Reversing Auto magnetic 9 Jog Selector Switch B Input Options 14 Master Override Board 17 Adj Linear Accel Decel 22 Tach Follower 25 Ext MA Signal Isolated 33 Spee...

Page 17: ...trations Section VII Max Control Proj 65 1 35 Circuit Breaker Operator Panel Mounting Slot Width 25 8 59 9 34 12 00 1 33 1 20 1 75 6 00 10 55 6 30 25 9 06 16 81 Conduit Entrance 3 4 14 N P T 4 Places...

Page 18: ...5 1 75 6 00 1 20 Conduit Entrance 3 4 14 N P T 6 Places 25 00 Approx 9 34 3 75 Approx 9 34 1 33 8 59 1 35 8 Mounting Slots 25 Wide 9 06 16 81 10 55 Figure 2 Approximate Weights VEL Controls 30 Pounds...

Page 19: ...19 P 3026 Doc No 60881 Boston Gear Ratiotrol DC Motor Speed Control Illustrations Section VII Ratiotrol D C Systems Figure 3 VEL VEH Series...

Page 20: ...2 AC1 11 8 9 E3 E19 E20 VEL 50VDC Field VEH 100VDC Field F F CB1 30A RV1 L1 L2 115V 230V 115V 115V Blk Wht T1 Power Bd Blk Red Blk Wht 24V 20V 20V 2 1 5 4 3 K1 E10 E13 13 E11 E12 12 14 15 D1 D2 D4 D3...

Page 21: ...action for direct or consequential damages to property or person The foregoing limited warranty is expressly made in lieu of all other warranties whatsoever express implied and statutory and includin...

Reviews: