Bosch Worcester Greenstore 180 Instruction Manual Download Page 4

GENERAL INSTALLATION

COLD MAINS PIPEWORK

Run the cold main through the building to where the

Greenstore cylinder is to be installed. Take care not to run the cold 

pipe near hot water or heating pipe work to minimize heat pick up.

Identify the cold water supply pipe and fit an isolating valve (not

supplied)
A 22mm BS1010 stopcock can typically be used but a 22mm 

quarter turn full bore valve is preferred as it does not restrict the 

flow as much.  Do not use “screwdriver slot” or similar valves.
Position the inlet control just ABOVE the Temperature & Pressure

Relief Valve (TPRV) mounted on the top of the cylinder. This 

ensures that the cylinder does not have to be drained down in 

order to service the inlet control set.

Check that the arrow points in the direction of the water flow.
Mount the expansion vessel in a suitable position on the wall using 

the bracket provided. Use the hose to connect to the inlet control 

group.

Ensure that the top of the vessel is accessible for servicing.

BALANCED COLD CONNECTION

Where there are showers, bidets or monobloc taps in the 

installation then a balanced cold supply is necessary.

There is a 22mm balanced connection on the inlet control set.

Another method is to split the inlet control set on to two parts.

Site the pressure reducing valve immediately after the incoming 

cold mains stopcock (typically under the kitchen sink.) All outlets in 

the house will be at 3 bar and thus automatically balanced.

The expansion relief valve section must still be mounted just above

the TPRV on the cylinder.  A 3/4”F-22mm compression adaptor 

will be needed (not supplied)

HOT WATER PIPEWORK

Run the first part of the hot water distribution pipework in 22mm. 

This can be reduced to 15mm and 10mm as appropriate for the 

type of tap etc. Your aim should be to reduce the volume of the hot 

draw-off pipework to a practical minimum so that the time taken for 

the hot water is as quick as possible.
Do not use monobloc mixer taps or showers if the balanced cold

connection is not used. The unit will back pressurize the cylinder 

and result in discharge.

PRIMARY COIL CONNECTIONS

Connect the primary connections (Indirect only) using the

compression fittings provided for connection to the Worcester 

Heat Pump only.
It is preferred that the primary circuit is a sealed system with a

maximum pressure of 2.5 bar.  An additional expansion vessel and 

safety valve would be required in this case.
The supplementary coil is for use with Worcester Solar Systems 

exclusively that are equipped with Worcester solar controls. 

Please refer to the installation manuals, Greenstore System 

Installation manual and Worcester Greenskies Solar literature:

NOTE:
The relief valve connection should not be used for any 
other purposes.

        GENERAL INSTALLATION

Worcester Bosch Grrenstore

Summary of Contents for Worcester Greenstore 180

Page 1: ...EENSTORE Indirect Unvented Cylinder with Solar Coil FOR USE WITH WORCESTER GREENSTORE SYSTEM HEATPUMP ONLY GB IE WORCESTER GREENSTORE 180 CYLINDER SOLAR COMPATIBLE WORCESTER GREENSTORE 280 CYLINDER SOLAR COMPATIBLE ...

Page 2: ...linder is supplied complete with all the necessary pre adjusted safety and control devices needed to connect to the cold water supply mains High quality controls have been selected to combine high flow rate performance with minimum pressure drop to allow the Greenstore cylinder to perform well in areas where there is a minimum dynamic working mains pressure of 1 5 bar Greenstore cylinders are KIWA ...

Page 3: ... flowrate is not being achieved SITING THE UNIT Outlets that are above or at some distance from the Greenstore cylinder can still be supplied with water Outlets above the Greenstore cylinder will reduce the outlet pressure available by 0 1 bar for every 1 metre of height difference Site the unit to minimise dead leg distances especially to the point of most frequent use The unit should be protected...

Page 4: ...tely after the incoming cold mains stopcock typically under the kitchen sink All outlets in the house will be at 3 bar and thus automatically balanced The expansion relief valve section must still be mounted just above the TPRV on the cylinder A 3 4 F 22mm compression adaptor will be needed not supplied HOT WATER PIPEWORK Run the first part of the hot water distribution pipework in 22mm This can be...

Page 5: ...minate in a safe place where there is no risk to persons in the vicinity of the discharge and positioned safely from electrical devices have a vertical section of pipe at least 300 mm long below the Tundish before any elbows or bends in the pipework installed with a continuous fall visible at both the tundish and the final point of discharge or where this is not possible or practically difficult the...

Page 6: ...R DRAINED OFF MAY BE VERY HOT DRAINING Isolate the unit from the cold mains Open a hot water tap at the lowest position in the building to reduce the pressure Remove the mains water inlet connection Attach a flexible hose to the connection on top of the cylinder ensuring the hose reaches to a level well below the unit The greater the difference in elevation the greater the flow rate and the maximum ...

Page 7: ...eat Pump HW Sensor cable entry 180 280 LITRE CYLINDERS WITH SOLAR COIL Air Vent Connecting hot water sensor GT3 Before carrying out any electrical connections ensure that the Heat Pump is isolated from the mains supply Remove the Heat Pump front cover and route the sensor cable from the back of the Heat Pump laying the sensor cable onto the cable tray Connect the sensor to terminals GT3X on the te...

Page 8: ...arge 3 0 bar Expansion relief valve setting 6 0 bar PART No CAPACITY HEIGHT WIDTH DEPTH WEIGHT kg empty WEIGHT kg full 7 716 180 017 180 L 1520 600 650 97 387 7 716 180 018 280 L 1700 695 695 136 596 All Dimensions are of the cased unit and are in mm Approvals KIWA Approved to the Water Regulations KIWA Approved to Building Regulations G3 L1 8 Worcester Bosch Greenstore 280 litre cylinder storage ...

Page 9: ...r WHERE IS OPERATING PRESSURE REDUCING VALVE SITUATED HAS THE EXPANSION VESSEL OR INTERNAL AIR SPACE BEEN CHECKED YES NO WHAT IS THE HOT WATER TEMPERATURE AT THE NEAREST OUTLET oC THERMAL STORES ONLY WHAT IS THE OPERATING SETTING OF THE PRESSURE REDUCING VALVE Where fitted bar WHERE IS THE PRESSURE REDUCING VALVE SITUATED WHAT STORE TEMPERATURE IS ACHIEVABLE oC WHAT IS THE MAXIMUM HOT WATER TEMPERA...

Page 10: ...ENGINEER NAME COMPANY NAME TEL No CORGI ID SERIAL No COMMENTS SIGNATURE SERVICE 3 DATE ENGINEER NAME COMPANY NAME TEL No CORGI ID SERIAL No COMMENTS SIGNATURE SERVICE 4 DATE ENGINEER NAME COMPANY NAME TEL No CORGI ID SERIAL No COMMENTS SIGNATURE SERVICE 5 DATE ENGINEER NAME COMPANY NAME TEL No CORGI ID SERIAL No COMMENTS SIGNATURE SERVICE 6 DATE ENGINEER NAME COMPANY NAME TEL No CORGI ID SERIAL No...

Page 11: ...Worcester Bosch Greenstore 11 NOTES NOTES ...

Page 12: ...of BBT Thermotechnology UK Ltd www worcester bosch co uk User and Installation Instructions Greenstore Cylinder Solar Compatible 8 716 113 377b 2007 01 EN CONTACT INFORMATION WORCESTER BOSCH GROUP TECHNICAL 08705 266241 SERVICE 08457 256206 SPARES 01905 752576 LITERATURE 01905 752556 TRAINING 01905 752526 SALES 01905 752640 WEBSITE www worcester bosch co uk ...

Reviews: