Does the electrode
spark at the burner?
No
Does the
fan stop
after a few
seconds?
No
Remove electrical
connectors from the
pressure switch and
restart the boiler. Is
there continuity
across the two switch
terminals when the
fan runs?
Pressure switch
has not closed.
Are the silicone
tubes in good
condition and
free of
condensation?
Replace tubes.
If condensation has
occurred also replace
pressure switch and
check condition of
venturi in the fan.
No
No
Yes
Inspect the flue.
Is it free of
restrictions?
Replace air pressure
switch.
NOTE: In the unlikely
event of this not
solving the problem.
Inspect the pressure
pick up (venturi)
in the fan.
Yes
No
Rectify flue
problem
Yes
Is there continuity
on the two green
wires?
No
Repair or replace
harness.
Yes
Replace control board.
(Section 15.4.9)
Yes
Yes
Boiler has
LOCKED OUT
(probably due to
overheating). Is
the boiler fully
water
pressurised and
is all air vented.
Yes
Switch off mains
supply and remove
boiler front panel and
combustion chamber
cover. Inspect the
primary (red) sensor.
Is it fixed securely to
the pipe?
Rectify fault.
No
Remove Molex
connector at X3. Is
there continuity
across the two orange
wires? (ensure black
overheat stat is cool).
Yes
Re-fix sensor to pipe.
No
No
Replace overheat
thermostat or
harness to it.