4.2.2
AutoDome Pendant Arm Mount
Alarms and Relay Connections | en
31
3.
From the AutoDome main menu, select Alarms Setup>Inputs Setup, and set the Alarm
Input # to N.O.S. See the table below for contact and condition details.
AutoDome Programmed N.O.S.
Contact
Alarm Condition
Open
Normal
Closed
Alarm
Cut or brake
Tamper
Configuring a Normally Closed Supervised Alarm
1. Install a 2.2 K end-of-line resistor in the alarm circuit.
2. Connect the alarm wires to input 1 or 2 (pin 5 or 6) and to the ground (pin 7) at the
AutoDome.
2.2K
Figure 4.2
N.C.S. - Normally Closed Supervised Connections
3.
From the AutoDome main menu select Alarm Setup>Inputs Setup, and set Alarm Input #
1
Dry Contact
3
Dome Connector
2
Alarm 1 or 2 only (Pin 5 or 6)
4
Ground (Pin 7)
to N.C.S. See the table below for contact and condition details.
AutoDome Programmed N.C.S.
Contact
Alarm Condition
Open
Alarm
Closed
Normal
Short
Tamper
4.3
Configuring Non-supervised Alarms (inputs 1 through 7)
You can configure alarms 3 through 7 as non-supervised Normally Open (N.O.) or Normally
Closed (N.C.) alarms.
4.3.1
Configuring a Normally Open Non-supervised Alarm
1. Connect the alarm to the appropriate input (1 through 7) and ground at the AutoDome.
Figure 4.3
N.O. - Normally Open Non-supervised Connections
1
Dry Contact
3
Dome Connector
2
Alarm Inputs 1 to 7
4
Ground