PROFIBUS-DP interface
3–1
1070 066 091-102 (01.08) GB
3
PROFIBUS-DP interface
Section 3 contains a description of
D
the drive modes that can be used with the PROFIBUS-DP interface (cf.
page 3–2 ff),
D
the initialization (cf. page 3–12 ff),
D
cyclic operation (cf. page 3–16 ff), and
D
the available diagnostic data of the PROFIBUS-DP interface (cf.
3.1
Characteristics
Standards:
IEC 1158-2
Interface type:
PROFIBUS-DP
PROFIBUS services: Write_Read_Data/Data_Exchange (Default_SAP)
Read_Inputs
(SAP56)
Read_Outputs
(SAP57)
Global_Control
(SAP58)
Get_Config
(SAP59)
Slave_Diagnosis
(SAP60)
Set_Param
(SAP61)
Check_Config
(SAP62)
.
For more information concerning the hardware setting of PROFIBUS
interface X51 (address, mode), please refer to page 2–4.
Please note that the PROFIBUS address can only be set using rotary
switches S2/S3, not via the PROFIBUS service ”Set_Slave_Address”
(SAP55).