RADION receiver OP
RADION repeater | en
19
Bosch Security Systems, Inc.
Reference Guide
2014.12 | 02 | F.01U.261.835
Power/Voltage
(Standby battery)
16.5 VAC, 40VA (~)
(EN voltage range: 16.5 VAC– 18 VAC) AC Type (device)
Rated 3.7 VDC, 3050mAH EVE ENERGY CO Part No P0046-LF (Not user
replaceable). For standby battery to be operative, the tamper switch is
required to be engaged.
Power source type: A
Low battery level: 3.5V
Transformer power/voltage
Must meet country specific requirements
Current Draw
60 mA
Wire Gauge
0.65 mm (22 AWG) to 2.0 mm (18 AWG)
Temperature (operating)
Functional range: -10*C to +49*(+14*F to +120*F)
EN 50130-5 Class II only: -10*C to 40*C (+14*F to +104*F)
Relative Humidity
0% to 93% (non-condensing)
Device testing
To ensure proper functionality, the device must be tested at least once
every year by an installer.
Wall and Cover Tamper Switch Transmits a tamper signal when someone removes the device from its
base or pulls it away from the wall.
Frequency
433.42 MHz
Table 4.5: Specifications
4.4
LEDs
The repeater utilizes an external LED indicator to status the operation of the repeater. Refer to
the table below for LED descriptions.
LED Condition
Pattern Description
On (Normal)
–
Indicates the repeater is functioning normally.
Off
–
Indicates there is a power failure to the repeater, or that the
receiver is not wired correctly.
Continuous Flash: 1 sec
rate for 5 sec
–
Indicates the repeater is being powered up, and conduction
manufacturing test initializations.
Continuous Flash: A 3-
pulse signal, followed by
a short delay after the 3
rd
pulse
–
Indicates the repeater has experienced a low battery
condition.
Continuous Flash: A 2
flash pattern continuous
pulse between On and
Off states with a short
delay after the 2
nd
pulse
–
Indicates an AC power failure is detected.
–
A communication failure within internal hardware
components inside the receiver