11 Quick Start
11.1 Checklist before Quick Start
11.1.1 Step 1: Check application conditions
Rated ambient temperature
-10...40 ℃
Derating / ambient temperature
1.5 % / 1 °C (40...50 °C)
Rated storage temperature
-20...60 ℃
Rated altitude
≤ 1,000 m
Derating / altitude
1 % / 100 m (1,000...2,000 m)
Mounting mode
Wall mounting
Tab. 11-1: Application conditions checklist
chapter 6.1.8 "Conditions" on page 21
.
11.1.2 Step 2: Check mounting conditions
Converter mounting direction
Vertical
Minimum top space
d
top
= 150 mm
Minimum bottom space
d
bot
= 150 mm
One converter is arranged above another
Air guide available is required in between
Mounting screws
2 x M4 or 4 x M4, no loose screws
Tab. 11-2: Mounting conditions checklist
chapter 7.1 "Installation Conditions" on page 26
11.1.3 Step 3: Check the wiring
Mains connection
Connect L1, L2, (L3) of converter to mains accordingly
Motor connection
Connect U, V, W of converter to motor accordingly
Grounding
Must be securely connected
Shielding
Must be securely connected
Power cables
Must observe
chapter 8.1 "Wiring Diagram" on page 31
Control terminals connection
Must be securely connected
Control cables
Must observe
chapter 8.2.2 "Control Cables" on page 35
EMC
Must observe
chapter 9 "Electromagnetic Compatibility
Switches
Must be switched off
Load
Must be disconnected
Tab. 11-3: Wiring checklist
VFC 3210
Bosch Rexroth AG
Quick Start
DOK-RCON04-VFC3210****-IT01-EN-P
69/253