6.1.7 Protection
Over current protection, over- / under- voltage protection, surge current / short circuit protection, in-
put / output phase loss protection, converter over- / under- temperature protection, motor overload
protection, motor over temperature protection, direction lock protection, analog input broken wire de-
tection, etc.
6.1.8 Conditions
Rated ambient temperature
-10...40 ℃
Derating / ambient temperature
1.5 % / 1 °C (40...50 °C)
Rated storage temperature
-20...60 ℃
Rated altitude
≤ 1,000 m
Derating / altitude
1 % / 100 m (1,000...2,000 m)
Relative humidity
≤ 90 % RH (No condensation)
Degrees of protection
IP 20 (Mounting on the metal wall in control cabinet )
Degrees of pollution
2 (EN 50178)
Vibration
10 Hz ≤ f ≤ 57 Hz amplitude: 0.075 mm
57 Hz < f ≤ 150 Hz acceleration: 1 g
Mounting mode
Wall mounting
Cooling type
Natural cooling (≤ 0K75)
Enforced air cooling (≥ 1K50)
Certification
CE
VFC 3210
Bosch Rexroth AG
Frequency Converter Overview
DOK-RCON04-VFC3210****-IT01-EN-P
21/253