7.10.6 Pump Thermal Protection
Code
Name
Setting range
Default Min.
Attri.
F4.03 Pump function configuration word
0...63
Bit0: Pump power limit
Bit1: Pump thermal protection
Bit2: Switch master to slave
Bit3: Two points / double pump
Bit4: Pressure drop / overshoot
compensation
Bit5: Activating myCro
0
-
Stop
F4.36 Pump thermal protection speed
0…5,000 rpm
500
1
Stop
F4.37 Pump thermal protection time
constant
0…6,000 s
0
1
Stop
Tab. 7-24: Parameter list of pump thermal protection
The pump may overheat at a low speed due to the oil volume required for the
pump cooling may not be adequate. The pump thermal protection function will
detect if pump speed is lower than the speed limitation [F4.36], and trigger
warning or error message according to [F4.37]. For details reference the follow-
ing table and figure.
This function can be activated by bit1 of F4.03 and is only active if drive is in op-
eration.
Protection condition
F4.36 (protection speed) = 0rpm F4.36 (protection speed) > 0rpm
F4.37 (protection time) = 0s
Inactive
Warning
F4.37 (protection time) > 0s
Inactive
Error
Tab. 7-25: Protection condition