The continuous current of the drive controller should be greater
than the continuous current of the motor.
The continuous power of the drive controller must be greater than
the required average power!
Selecting the Connection Technique
For the available power cables and encoder cables, see documentation
"Rexroth Connection Cables IndraDrive and IndraDyn".
Notes on Commissioning
For further information, notes on commissioning and supporting
documents (e.g., forms for entering the required data) see firm‐
ware documentation.
4.3.5
Cables
Motor power cables
Selection
How to select a suitable motor power cable:
See documentation "Rexroth Connection Cables IndraDrive and IndraDyn"
(R911322949).
Allowed cable lengths
Allowed cable lengths at ambient temperature T
a_work
≤ 40 °C according to
EN 60 204:
HCS01.1E-…-A-02
PWM frequency [kHz]
4
8
12
16
W0003
40 m
20 m
15 m
5 m
W0006
W0009
W0013
W0018
HCS01.1E-…-A-03
W0005
W0008
W0018
W0028
W0054
75 m
38 m
25 m
-
Tab. 4-11:
Allowed motor cable lengths
DOK-INDRV*-HCS01******-PR05-EN-P
Bosch Rexroth AG
53/341
Rexroth IndraDrive CsDrive Systems with HCS01
Combining the individual components