5.3.2
Power routing 400 V
PE PE PE
PE
PE
PE
6 mm² (green/yellow)
16 mm² (green/yellow)
Min. 16 mm² (green/yellow)
PE neutral point
230V
400V
4 mm² (green/yellow)
16 mm² (green/yellow)
4 mm² (green/yellow)
Fuses, better: protective motor switches
e.g. drives
Transformer
acc. to EN 60742
W1 N
V1
U1
L1 L2 L3 N
Leads
L1.1 L2.1 L3.1 N
PE
PE
N
U2
PE N1 U2
4 mm² (green/yellow)
Overvoltage
category II
230 V power supply
operator terminals
service plug receptacle(s)
N conductor:
Use only with
permission of
the operator!
=
+24 V
0 V
DC 24 V
L1.1 L2.1 L3.1 PE
PE
1
To the housing of the control cabinet
To the device
All housing parts (functional earth)
Overvoltage
category III
Power
supply unit
Terminals in
isolated
arrangement
Overvoltage
category I
Fig. 5-20:
Power routing 400 V
High electrical voltage! Danger to life and risk
of injury caused by electric shock or bodily
harm caused by supply voltage on the
protective extra-low voltage (e.g. +24 V)!
DANGER
Power supply units, whose net connection is designed for overvoltage
category III, can be connected to a net voltage with overvoltage category II or
overvoltage category III, see
fig. 5-20 "Power routing 400 V" on page 27
Danger to life and risk of injury caused by
connection of power supply units, which
cause protective extra-low voltage (e.g. +24
V), to supply voltages, for which they are not
designed.
DANGER
Power supply units, whose net connection is designed for overvoltage
category III, can be connected to a net voltage with overvoltage category II or
overvoltage category III, see
fig. 5-20 "Power routing 400 V" on page 27
Material damages to electronics due to
missing functional earth!
NOTICE
Ensure that the functional earth is connected, because otherwise the
electronics can be destroyed by a potential difference between the
VDP 16.3/40.3/60.3 and the PC if the voltage supply is interrupted to only
one device and established again. A direct connection between the functional
earth and the display VDP xx.3 and VPB 40.3 and VSB 40.3 is
recommended. If the functional earth is wired at a neutral point, also connect
the control cabinet PC (VPB 40.3, VSB 40.3) to this neutral point.
IndraControl VDP 16.3, VDP 40.3, VDP 60.3 Operator Display
27/57
Dimensions, Installation and Wiring
R911323862_Edition 07 Bosch Rexroth AG