background image

R911418823, Edition 01, 7 / 8

U

P

 24 V

GND

+

Input
Input

+

Fig. 9: 4-wire sensor
It  is  recommended  to  use  the  same  supply  for  the  voltage

supply of the sensor as for U

P

 of the module. The connection

via the potential distribution terminals XI821116, XI822116 or

XI824116 is the recommended connection.

9.3 Installation notes

NOTICE

Device destruction due to electrostatic discharge
The  device  contains  components  that  can  be  damaged

or  destroyed  by  electrostatic  discharge.  Comply  with  the

required  safety  measures  against  electrostatic  discharge

(ESD) acc. to EN 61340-5-1 when operating the module.

Mounting location
The module has the degree of protection IP 20 and is

thus intended for use in a closed control cabinet or con-

trol box (terminal box) with the degree of protection IP

54 or higher. The control cabinet has to be provided

with sufficient stability and rigidity (acc. to UL 61010-1,

61010-2-201).

End clamps
Fasten end clamps of the type SUP-M01-ENDHALTER

(R911170685) on both sides of the station. End clamps

ensure the correct fastening on the support rail and are

used as lateral end elements. Always fasten one end clamp

of the station before mounting the station. This ensures

the following:

It impedes the shifting of the modules

The installation place for the end clamps is secured.

Support rail
Mount the module on a 35 mm standard support rail.

Use only a TH 35-7.5 support rail acc. to EN 60715. The

fastening distance of the support rails may not exceed

200 mm. This distance is required to ensure stability while

mounting and dismounting the module.

< 200 mm

_

Provide the following minimum distances for sufficient

cooling:

35 mm

0 mm

0 mm

35 mm

35 mm

Fig. 10: Ventilation distance

Additionally, provide sufficient distance for mounting, dis-

mounting, plugs and cables.

If more devices are connected in series to the station on

the left or right, the surface temperature may not exceed

60° C

In case of a several line design, the supply air has to be

measured under each line and its limit value may not be

exceeded. For the permitted ambient temperatures, refer

to the chapter "Ambient conditions".

9.4 Mounting the ctrlX I/O module

NOTICE

Damage of the device by plug mounting under voltage!
Disconnect  the  module  and  all  connected  module  compo-

nents from voltage before mounting or dismounting.

NOTICE

Possible damage to property due to unintended mounting of

the support rail

Connect the support rail to a functional ground.

Mount the module on a support rail.

Install the module in a control cabinet or an appropriate

housing.

NOTICE

Module is not fixed correctly due to engaged support arm

mounting!
Before  mounting,  ensure  that  the  support  arm  mounting  of

the  control  is  not  in  open  position.  If  required,  release  the

clamping of the open position using the locking lever, refer to

the following figure 11.

NOTICE

Damage of the device by short circuit of patch connectors
There  is  an  endcover  on  the  right  of  the  bus  coupler  upon

delivery.  Remove  this  endcover  to  connect  the  modules  in

series  at  the  bus  coupler.  Position  the  endcover  on  the  last

module  of  the  station  to  protect  it  against  short  circuit  and

contamination.

 

Fig. 11: Locking lever to release the clamping of the open

position
Each module has to be snapped separately.

9.5 Positioning connector

1.

Position the connector on the connector holder, see 

.

2.

Engage the connector, see 

.

Summary of Contents for Rexroth ctrlX I/O XI312204

Page 1: ...cal data 3 1 General technical data XI312204 Number of inputs 4 Connection method Push in XI312204 Connection method 2 wire shielded twisted in pairs Signal type Differential Input signal 0 V to 10 V Input resistance 250 kΩ Limit frequency of input filter 12 8 kHz Conversion time 100 μs Resolution D A 16 bits incl sign Accuracy Typ 0 1 of the end value of the measured range MBE Max 0 3 of MBE Over...

Page 2: ...mi sinusoidal 15 g Broadband noise Acc to DIN EN 60068 2 64 20 500 Hz with 1 22 g RMS 30 min in all three axes For the current approvals go to www boschrexroth com electrics 4 For your safety 4 1 Intended use Only use the module as specified in the data sheet 4 2 User qualification The product use described in this data sheet is only intended for qualified electricians and staff trained by these q...

Page 3: ... the gain and the offset Value_Range The value range at the input of the User Scale calculation Scaled_Value_Range The desired value range at the output of the User Scale calculation Lower_Range_End_Value The value at the lower end of the input value range Scaled_Lower_Range_End_Value The desired value at the lower end of the output value range The values for gain and offset are calculated as foll...

Page 4: ... 6010 6020 6030 Channel 1 2 3 4 60x0 01 Value Int16 IN mV 60x0 02 Underrange Bit IN W 0x2360 60x0 03 Overrange Bit IN W 0x8910 60x0 04 Limit 1 2Bit IN Bit0 Value Limit 1 Bit1 Value Limit 1 60x0 06 Limit 2 2Bit IN Bit0 Value Limit 2 Bit1 Value Limit 2 Index hex Object name Data type Direc tion Error warning informa tion Diagnostic number description Unit A000 0 Material number String 20 IN A010 0 F...

Page 5: ...input value and the diagnostic data in the Compact representation Word 1 INT IN Channel 1 Value Word 2 INT IN Channel 2 Value Word 3 INT IN Channel 3 Value Word 4 INT IN Channel 4 Value Word 5 Byte 1 Byte 2 Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 5 Bit 6 7 Bit 2 Bit 3 Bit 4 5 Bit 6 7 IN IN IN IN IN IN IN IN IN IN IN IN Periphery voltage ok Error Channel 1 Wire break Channel 1 Overrange Channel 1 Limit 1 Cha...

Page 6: ...or peripheral voltage error RD RD RD RD RD RD RD RD RD RD Communication or configura tion error RD RD RD RD RD Table 3 Module status LED diagnostic and device status 8 5 Channel status LED Each input channel of the module is provided via a channel status LED at the plug Refer to Chapter 3 2 Clamping point assignment on page 1 Meaning of the channel LED LED Meaning Red Signal error Overrange or und...

Page 7: ...vide the following minimum distances for sufficient cooling 35 mm 0 mm 0 mm 35 mm 35 mm Fig 10 Ventilation distance Additionally provide sufficient distance for mounting dis mounting plugs and cables If more devices are connected in series to the station on the left or right the surface temperature may not exceed 60 C In case of a several line design the supply air has to be measured under each li...

Page 8: ... to be met Use only insulated copper wires suitable for at least 60 C 9 7 Dismounting module For dismounting use a common tool such as a slotted screwdriver with a 2 5 mm blade NOTICE Destruction of components and devices due to mounting and dismounting under voltage Disconnect the module and all connected module compo nents from voltage before mounting or dismounting Removing module from support ...

Reviews: