 LNL-500 

 Intelligent System Controller 

 

Quick Reference Guide 

 

 

 

 

For detailed information, please refer to the LNL-500 tab in the READYKEY

PRO 

Hardware Installation 

Guide (49289). 

1.0  The ISC Board 

The ISC board contains the following 
components (Refer to Figure 1):  

A.  two (2) unsupervised alarm inputs  
B.  one (1) RS-232 or RS-485 interface 
C.  two (2) downstream RS-485 interfaces 

(which can consist of one 4-wire and 
two 2-wire interfaces) 

D.  a set of three (3) status LEDs 
E.  one (1) bank of eight (8) dip switches 
F.  eleven (11) jumpers 
G.  one (1) power-in input 
H.  and one (1) memory backup  

(3 volt lithium) battery 

I. 

one (1) TCP/IP Connector 

 

Figure 1: LNL-500 

1.1 

Unsupervised Alarm Input Wiring 

GND

CABINET

TAMPER

POWER

FAULT

GND

IN2

IN1

 

Figure 2: Unsupervised Alarm Input Wiring 

 

If either of these inputs is not used, a jumper 
wire should be installed. 

If RS-485 communication is used, an RS-232 
to RS-485 converter is required at the host 
workstation. 

Summary of Contents for READYKEY PRO LNL-500

Page 1: ...faces which can consist of one 4 wire and two 2 wire interfaces D a set of three 3 status LEDs E one 1 bank of eight 8 dip switches F eleven 11 jumpers G one 1 power in input H and one 1 memory backup 3 volt lithium battery I one 1 TCP IP Connector Figure 1 LNL 500 1 1 Unsupervised Alarm Input Wiring GND CABINET TAMPER POWER FAULT GND IN2 IN1 Figure 2 Unsupervised Alarm Input Wiring If either of t...

Page 2: ...R R R SG PORT 1 CONFIGURED AS RS 485 TXD TR1 RXD TR1 GND CTS R1 RTS R1 TXD TR1 RXD TR1 GND CTS R1 RTS R1 2 WIRE TO RS232 RS485 CONVERTER TO RS232 RS485 CONVERTER To PC RS 485 2 Wire Configuration RS 485 4 Wire Configuration RS 232 Direct Connection Figure 3 Upstream Host Communication Wiring Port 1 If Using A 12 VDC Power Source Be Sure To Observe Polarity VIN GND 12 to 24 VDC Figure 4 Power Sourc...

Page 3: ...P Switch Address 1 2 3 4 Default 0 OFF OFF OFF OFF 1 ON OFF OFF OFF 2 OFF ON OFF OFF 3 ON ON OFF OFF 4 OFF OFF ON OFF 5 ON OFF ON OFF 6 OFF ON ON OFF 7 ON ON ON OFF Table 4 Processor Address 2 2 Communication Handshake Status HANDSHAKE STATUS DIP SWITCH 5 Transmit enabled by CTS ON Default None off Table 5 Handshake Status 2 3 Communication Baud Rate upstream and downstream DIP SWITCH BAUD RATE 6 ...

Page 4: ...n J7 2W 4W 2 Wire Configuration for Jumper J7 J7 2W 4W 4 Wire Configuration for Jumper J7 Figure 6 Port 1 RS 485 Type J3 J5 J6 J9 J4 RS 232 Configuration for Jumpers J3 J4 J5 J6 J7 J9 J3 J5 J6 J9 J4 RS 485 Configuration for Jumpers J3 J4 J5 J6 J7 J9 J8 J11 EOL Terminator On Configuration for Jumpers J8 J10 J8 J11 EOL Terminator Not On Configuration for Jumpers J8 J10 Figure 7 Communication Interfa...

Reviews: