5.1.7.4 Switching output x: Switch-on delay
In the menu Advanced functions
efx
further settings can be made for the switching
output x. The submenu can be found on the second submenu level.
The switching and switch-back delay prevents the alarm from responding too
frequently in unstable conditions. The switching delay is set in the following menu:
The following options are available:
Setting range: 0…100 seconds
Time period in seconds in which the signal must be permanently present
for the switching output to respond.
Notice:
▶
If the switching output OUT x has been assigned the window
function, the set value corresponds to the switch-on delay which
detects a valid reaching of the measuring window.
▶
If the switching output OUT x has been assigned the frequency
output function, this value has no effect.
5.1.7.5 Switching output x: Switch-back delay
The switch-back delay is set in the following menu:
The following options are available:
Setting range: 0…100 seconds
Delay of the switch-back signal for OUT x.
Time period in seconds in which the signal must be permanently present
for the switching output to respond.
Notice:
▶
If the switching output OUT x has been assigned the window
function, the set value corresponds to the switch-on delay which
detects a valid leaving of the measuring window.
▶
If the switching output OUT x has been assigned the frequency
output function, this value has no effect.