84
en | Configure the system
PRAESENSA
2020-09 | V1.20 | PRAESENSA 1.20
Configuration manual
Bosch Security Systems B.V.
5.7
Action definitions
On the Action definitions pages specific device functionality can be configured, e.g. the
buttons of the call station (extension), control inputs of the multifunction power supply and
the virtual control inputs of the system controller.
The process of configuring an action to a button or control input consists of two steps:
1.
Assigning an operation, page 84
2.
See the following sections to configure the actions per device type category:
–
–
Multifunction power supply, page 93
–
5.7.1
Assigning an operation
The operation specifies how the control input deals with incoming signals or how the button
reacts when it is pressed and released. An operation is always linked to a function (see
Assigning a function, page 85).
Type of operations
The available type of operations are represented in the following table:
Operation type
Description
Momentary - abort on release
The action
coupled to the control input or button is
active during the time the external contact is closed.
When the external contact is opened, the action is
immediately aborted.
Momentary - finish on release
The action
coupled to the control input or button is
active during the time the external contact is closed.
When the external contact is opened, the action is
stopped after the completion of the current phase.
When
the external contact is closed again while the
action is still running, the action is immediately aborted.
Toggle - abort on switch off
The action
coupled to the control input or button is
started when the external contact closes and
immediately aborted when the external contact closes
again.
Toggle - finish on switch off
The action
coupled to the control input or button is
started when the external contact closes. When the
external contact closes again, the action is stopped after
the completion of the current phase.
When
the external is closed a third time while the action
is still running, the action is immediately aborted.
Do once
The action
is started when the external contact closes.
The action
can be stopped with an Abort phased
announcement or Finish phased announcement.
Usually
, the Abort/Finish phased announcement