background image

Networking Cards

 Installation | en

11

Bosch Security System, Inc.

Installation Manual

F.01U.214.374 | 01 | 2012.08

4

Installation

4.1

General considerations

4.2

Mounting

The main board allows for the installation of one networking card. 
1.

Position the networking card along the bottom of the mainboard keypad with the 
connections aligned with the slot.

2.

Press down softly until the snap-fit hook locks into place ensuring that the connections 
seat into the slot properly.

CAUTION! 

Electrostatic discharge! 
Ground yourself using a wrist strap or take other suitable actions.
The FPA-1000 circuit boards have static-sensitive components that could become damaged. 
Run the ground wire to the enclosure before handling these circuit boards. Touch ground 
before unpacking and handling the circuit boards. This discharges any static electricity in your 
body. Continue touching the enclosure while installing the circuit boards.

DANGER! 

Before installing the networking card, remove all AC and battery power from the fire panel.

Summary of Contents for -NF

Page 1: ...Networking Cards FPE 1000 NE NF NW en Installation Manual ...

Page 2: ......

Page 3: ...00 Fire Panel Para obtener documentación adicional incluyendo los documentos en idiomas distintos del Inglés vea este CD incluido con la central de incendios FPA 1000 Para obter documentação adicional incluindo documentos em outros idiomas além do Inglês consulte este CD fornecido com o Painel de Incêndio FPA 1000 สําหรับเอกสารเพิ มเติมรวมทั งเอกสารในภาษาอื นที ไม ใช ภาษาอังกฤษให ดูซีดีแผ นนี ที ม...

Page 4: ...4 FPE 1000 NE NF NW F 01U 214 374 01 2012 08 Bosch Security System Inc ...

Page 5: ...al considerations 9 3 2 Ground Fault Detection 9 3 3 Port supervision 9 4 Installation 11 4 1 General considerations 11 4 2 Mounting 11 5 Connection 13 5 1 General considerations 13 5 2 Class A connections 13 6 Technical Data 15 6 1 Common parameters of all three networking cards 15 6 1 1 Environmental 15 6 1 2 Mechanical 15 6 2 FPE 1000 NE Ethernet Networking Card parameters 15 6 2 1 Electrical 1...

Page 6: ...UT NOT LIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE THE ENTIRE RISK AS TO THE QUALITY AND PERFORMANCE OF THE PROGRAM IS WITH YOU SHOULD THE PROGRAM PROVE DEFECTIVE YOU ASSUME THE COST OF ALL NECESSARY SERVICING REPAIR OR CORRECTION IN NO EVENT UNLESS REQUIRED BY APPLICABLE LAW OR AGREED TO IN WRITING WILL ANY COPYRIGHT HOLDER OR ANY OTHER PARTY WHO MAY ...

Page 7: ...E IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE THE ENTIRE RISK AS TO THE QUALITY AND PERFORMANCE OF THE LIBRARY IS WITH YOU SHOULD THE LIBRARY PROVE DEFECTIVE YOU ASSUME THE COST OF ALL NECESSARY SERVICING REPAIR OR CORRECTION IN NO EVENT UNLESS REQUIRED BY APPLICABLE LAW OR AGREED TO IN WRITING WILL ANY COPYRIGHT HOLDER OR ANY OTHER PARTY WHO MAY MODIFY AND OR REDIST...

Page 8: ...network is communicated to all the panels in the network Based on communication connection mode there are three types of networking cards available Table 2 1 Networking Card Types Type Number Description Connection Mode Maximum Distance FPE 1000 NE Ethernet Networking Card 3 Ethernet ports CAT 5 minimum 328 ft 100 m FPE 1000 NF Fiber Optic Networking Card 1 Ethernet port CAT 5 minimum 328 ft 100 m...

Page 9: ...work Port Identification For Ground Fault Detection to work properly one and only one end of a communication connection cable joining two networking cards must be Ground Fault Detection enabled To facilitate this the wired card FPE 1000 NW and the fiber optics card FPE 1000 NF each have a jumper located near the back of the Ethernet IN port Port 1 on the wired card and Port 3 on the fiber optic ca...

Page 10: ...10 en Planning Networking Cards F 01U 214 374 01 2012 08 Installation Manual Bosch Security System Inc Browser based Operation and Programming Networking in the FPA 1000 Installation and Operation Guide ...

Page 11: ...lace ensuring that the connections seat into the slot properly CAUTION Electrostatic discharge Ground yourself using a wrist strap or take other suitable actions The FPA 1000 circuit boards have static sensitive components that could become damaged Run the ground wire to the enclosure before handling these circuit boards Touch ground before unpacking and handling the circuit boards This discharges...

Page 12: ...llation Manual Bosch Security System Inc Figure 4 1 Mounting a Networking Card 1 Networking Card 2 Connectors and slot 3 Snap fit hook _ A a Gas Alarm Silenced Power Trouble Fire Alarm Supervisory DRILL RESET SILENCE ACK BATT RELAY3 RELAY2 RELAY1 ETHERNET AC IN 3 2 1 ...

Page 13: ...d nonpower limited circuit wiring must remain separated in the cabinet by at least 0 25 in 64 mm and must enter and exit from the cabinet through different knockouts or conduits Phone lines are generally considered to be nonpower limited so the cables for networking cards should not be run through the same knockout as the phone lines Avoid shielded or twisted pair wire except for special applicati...

Page 14: ... not share the same conduit or cable as the outgoing side of the loop 4 Refer to NFPA 72 for additional requirements of Class A circuits Figure 5 1 Network Connections Example Terminal Specifications Class A Style 7 FPE 1000 NW Wired OUT Terminals used for outgoing loop Wired IN Terminals used for return loop Legend 1 Wire to Wire connection 2 Wire to Ethernet connection 3 Ethernet to Fiber Optic ...

Page 15: ...ing Card parameters 6 4 1 Electrical Environment Indoor dry Relative humidity 5 to 93 non condensing Temperature operating 0 C to 49 C 32 F to 120 F Dimensions 6 16 in x 2 87 in 1 20 in 156 5 mm x 73 mm x 30 5 mm Weight 3 13 oz 88 8 g Indicators Data communication Yellow LED one per port Link status Green LED one per port Power indication Green LED one per board Power supply 20 VDC to 28 VDC from ...

Page 16: ...16 en Technical Data Networking Cards F 01U 214 374 01 2012 08 Installation Manual Bosch Security System Inc ...

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ...Bosch Security System Inc 130 Perinton Parkway Fairport NY 14450 USA www boschsecurity us Bosch Security System Inc 2012 ...

Reviews: