Troubleshooting
|
37
LV Heat Pump Series
8 733 905 683 (2013/04)
LV Heat Pump Series
No compressor
operation but fan runs
X
Is fault LED Blinking
4 times?
Condensate fault - poor
drainage
Check condensate pan for high
water level. Check drain line for
blockages, double trapping or
inadequate trapping.
Condensate fault -
blocked return air
Check condensate pan for high
water level. Check air filter and
return air duct work for blockage.
Check that there is adequate space
between the return air opening and
walls or other obstructions on free
return applications.
X
X
Is fault LED Blinking
5 times?
Brown out fault - low
supply voltage
Check primary voltage - insure it is
within the limits listed on the unit
data plate.
Brown out fault -
overloaded control
circuit
Check control voltage - if it is below
18 V check accessories connected
to the unit and insure that they do
not exceed the VA draw shown on
page 11.
Brown out fault - bad
thermostat connection
Check that thermostat wiring is
proper gauge and length, that it is
not damaged and that all
connections at the thermostat and
heat pump are secure.
X
Is fault LED Blinking
6 times?
Freeze fault, air coil - no
or low air flow
Check fan motor for proper
operation.
Check air filter
Inspect air coil for dirt/debris
Check duct work - are dampers
closed or blocked?
Freeze fault, air coil -
blocked return air
Check that there is adequate space
between the return air opening and
walls or other obstructions on free
return applications.
Freeze fault, air coil - low
refrigerant
Check refrigerant pressure with
gauge set.
X
X
No fault LED -
contactor not
energized
Thermostat not calling
for compressor
operation
Ensure that the thermostat is on
and calling for "Y"
Bad thermostat
connection
Check "Y" connection from
thermostat. Insure that there is 24
VAC between "Y" and "C".
Loose wire to contactor
coil
Check wiring - insure that there is
24 VAC across the contactor coil.
Burned out contactor
coil
Test contactor with 24VAC
(between "R" and "C"). Ohm
contactor coil - an open circuit
indicates a burned coil.
UNIT TROUBLESHOOTING
Problem
Mode
Check
Possible Cause
Action