Standard Blower Motor
|
33
LV Heat Pump Series
8 733 905 683 (2013/04)
LV Heat Pump Series
Constant CFM ECM Blower Motor
Table 10: Electrical Data Table - Constant CFM ECM Blower Motor
MODEL
Voltage
Code
Rated
Voltage
Voltage
Min/Max
Compressor
Fan
Motor
Fan
Motor
HP
Total
Unit
FLA
Min
Circui
t
Max
Fuse
QTY
RLA
LRA
LV015
1
208-230/60/1
187/253
1
5.6
29
2.8
0.33
8.4
9.8
15
2
265/60/1
238/292
1
4.6
20
2.6
0.33
7.2
8.4
15
LV018
1
208-230/60/1
187/253
1
6.5
43
2.8
0.33
9.3
10.9
15
2
265/60/1
238/292
1
5.8
46
2.6
0.33
8.4
9.9
15
LV024
1
208-230/60/1
187/253
1
7.4
43
2.8
0.33
10.2
12.1
15
2
265/60/1
238/292
1
6.7
46
2.6
0.33
9.3
11.0
15
3
208-230/60/3
187/253
1
5.9
63
2.8
0.33
8.7
10.2
15
4
460/60/3
414/506
1
2.9
30
2.6
0.33
5.5
6.2
15
LV030
1
208-230/60/1
187/253
1
9.9
54
2.8
0.33
12.7
15.2
25
2
265/60/1
238/292
1
8.5
46
2.6
0.33
11.1
13.2
20
3
208-230/60/3
187/253
1
6.9
63
2.8
0.33
9.7
11.4
15
4
460/60/3
414/506
1
5.4
30
2.6
0.33
8
9.4
15
LV036
1
208-230/60/1
187/253
1
13
74
4.3
0.5
17.3
20.6
30
2
265/60/1
238/292
1
11.3
67
4.1
0.5
15.4
18.2
25
3
208-230/60/3
187/253
1
7.8
68
4.3
0.5
12.1
14.1
20
4
460/60/3
414/506
1
3.9
34
4.1
0.5
8
9.0
15
LV041
1
208-230/60/1
187/253
1
13.6
88
6.8
0.75
20.4
23.8
35
3
208-230/60/3
187/253
1
8.8
68
6.8
0.75
15.6
17.8
25
4
460/60/3
414/506
1
4.4
34
5.5
0.75
9.9
11.0
15
LV042
1
208-230/60/1
187/253
1
13.6
88
6.8
0.75
20.4
23.8
35
3
208-230/60/3
187/253
1
8.8
68
6.8
0.75
15.6
17.8
25
4
460/60/3
414/506
1
4.4
34
5.5
0.75
9.9
11.0
15
LV048
1
208-230/60/1
187/253
1
15.7
84
6.8
0.75
22.5
26.4
40
3
208-230/60/3
187/253
1
11
88
6.8
0.75
17.8
20.6
30
4
460/60/3
414/506
1
5.4
44
5.5
0.75
10.9
12.3
15
LV060
1
208-230/60/1
187/253
1
26.3
145
9.1
1
35.4
42.0
60
3
208-230/60/3
187/253
1
15.6
123
9.1
1
24.7
28.6
45
4
460/60/3
414/506
1
7.8
70
6.9
1
14.7
16.7
20
LV070
1
208-230/60/1
187/253
1
28.3
158
9.1
1
37.4
44.5
70
3
208-230/60/3
187/253
1
19.2
155
9.1
1
28.3
33.1
50
4
460/60/3
414/506
1
8.7
75
6.9
1
15.6
17.8
25