Troubleshooting
|
27
LM Series Heat Pump
8 733 905 315 (2013/9)
Revised 09-13
UPM Board LED Indications
Indication
Color
Blinks
Description
GREEN
Solid
18-30 VAC Power is present
RED
1
High pressure lockout
RED
2
Low pressure lockout
RED
3
Freeze sensor lockout
RED
4
Condensate overflow
RED
5
Brownout
RED
6
Evaporator Freeze condition
Comfort Alert Module -Flash Codes
Status LED
Status LED
Description
Status LED Troubleshooting Information Solution
YELLOW "ALERT"
FLASH CODE 3
Short Cycling
Compressor is
running only briefly
1. Thermostat demand signal is intermittent
2. Time delay relay or control board defective
3. If high pressure switch present go to Flash Code 2
information
4. If low pressure switch present go to Flash Code 1
information
YELLOW "ALERT"
FLASH CODE 4
Locked Rotor
1. Run capacitor has failed (may not be bad, verify)
2. Low line voltage (contact utility if voltage at disconnect
is low)
•
Check wiring connections
3. Excessive liquid refrigerant in compressor
4. Compressor bearings are seized
•
Measure compressor oil level
Summary of Contents for LM Series
Page 39: ...Wiring Diagrams 39 LM Series Heat Pump 8 733 905 315 2013 9 Revised 09 13 Figure 26 ...
Page 41: ...Wiring Diagrams 41 LM Series Heat Pump 8 733 905 315 2013 9 Revised 09 13 Figure 28 ...
Page 43: ...Wiring Diagrams 43 LM Series Heat Pump 8 733 905 315 2013 9 Revised 09 13 Figure 30 ...
Page 45: ...Wiring Diagrams 45 LM Series Heat Pump 8 733 905 315 2013 9 Revised 09 13 ...
Page 47: ...Wiring Diagrams 47 LM Series Heat Pump 8 733 905 315 2013 9 Revised 09 13 Figure 31 ...
Page 49: ...Wiring Diagrams 49 LM Series Heat Pump 8 733 905 315 2013 9 Revised 09 13 Figure 33 ...
Page 59: ...Notes 59 LM Series Heat Pump 8 733 905 315 2013 9 Revised 09 13 NOTES ...