Page 3: ... 8 Reading distances 13 2 Installation 15 2 1 General 15 2 1 1 Mechanical structure of the flush mount version 15 2 1 2 Mechanical structure of the surface mount version 15 2 2 Installing data and supply lines 16 2 3 Assembly preparation 17 2 4 Assembling the reader 18 2 5 Assembling the reader module 20 2 5 1 Configuring the reader DIP switches 20 2 5 2 Connecting and mounting the reader module 2...

Page 4: ... V 1 General 1 1 Introduction This installation manual is aimed at authorized service providers The installation manual contains instructions on the installation and configuration of the Bosch Security Systems proximity reader LECTUS select 1 2 3 4 5 6 7 8 9 C 0 E Figure 1 1 LECTUS select readers ...

Page 5: ... installed as part of an escape route and must have a fail safe lock the door must be released in the event of power loss Ideally a solenoid lock should be used an emergency switch with a glass cover for manual breaking the circuit so that the fail safe lock can be de energized immediately in an emergency Warning Risk of damage Protect the device against electrostatic discharge by observing the ES...

Page 6: ... should be enforced whenever there is a risk that failure of malfunction of the device might pose a risk to humans animals or damage to the equipment this must be prevented with additional safety measures limit switches protective equipment etc 1 3 Disposal Old electrical and electronic equipment This product and or battery must be disposed of separately from household waste Dispose such equipment...

Page 7: ...General en 7 Bosch Security Systems B V Installation manual 2021 02 01 F 01U 389 837 1 4 Components x1 x2 x2 Quantity Component 1 Reader module 1 Locking bar 4 Screws 1 Quick installation guide 2 Safety instructions ...

Page 8: ... reader and the control center takes place via an encrypted RS485 bus The reader has a compact design and is available in two variants with and without a keyboard each as a flush mount version The flush mounted variant fits into any device box in flush mounted or hollow wall design according to DIN with a device screw distance of 60 mm The readers have tamper monitoring and tear off detection i e ...

Page 9: ... 22 mm 1 mm 101 mm 93 4 mm 56 mm 3 5 mm 16 2 mm 21 2 mm Accessories for surface mount version ARA SELECT SWA ARA SELECT WWA Flush mount version 88 mm 19 mm 16 mm 2 mm 101 mm Wall bracket for flush mounting part included The wall bracket is included in the reader delivery 56 mm 7 mm 3 5 mm 50 5 mm 71 6 mm 14 5 mm 73 mm 26 2 mm 25 7 mm 56 mm 60 mm ...

Page 10: ...o 1 5 2 Phg_crypt The following readers support phg_crypt protocol Commercial Type Number CTN Description ARD SELECT BP Black phg_crypt ARD SELECT WP White phg_crypt ARD SELECT BPK Black phg_crypt Keypad ARD SELECT WPK White phg_crypt Keypad These readers are not compatible with AMC2 controllers Phg_crypt is a proprietary secure protocol that can be used in third party installations such as MATRIX...

Page 11: ...on manual 2021 02 01 F 01U 389 837 1 6 RFID technology The LECTUS select readers support the following RFID technology LEGIC prime Advant MIFARE Classic DESFire EV 1 The RFID technology that can be used is dependent on the reader configuration and the reader firmware ...

Page 12: ...DESFire NFC peer to peer target ISO 14443 B also NFC Forum Type 4B Tag according to ISO 14443 part 4 e g B InfineonSLE ISO 15693 also ISO 18000 3 mode 1 ATC128 MV ATC256 MV ATC1024 MV Selected types e g B EM 4035 Infineon SRF55VxxP Tag It HFI INSIDE Secure UID only according to INSIDE Secure Passive mode initiator Access with transparent mode assigned commands for MIFARE transponders If transponde...

Page 13: ...4096 JP10 JP11 ISO 14443A 2 LEGIC ATC1024 MV110 ISO 15693 6 5 3 5 Classic 1k 3 5 3 Classic 4k 4 DESFire EV1 2k 4k 8k 1 1 Legic CTC4096 MP410 prime access 6 5 4 Legic CTC4096 MP410 ISO14443 access 2 5 2 Key fob not available during the test AFS4096 not available as key fob Note Not all designs and transponder media were available at the time the distance was measured i Notice The reading distances ...

Page 14: ...ing distance Shade or shield the data carrier with metal such as EC card in your wallet key fob on your key ring etc No optimal coupling i e the antenna surface of the data carrier is perpendicular 90 to the antenna surface of the reader Data carrier itself key fob small active antenna surface bad response from the data carrier ID card key fob combination ID card e g LEGIC inductive MIFARE inducti...

Page 15: ...her or be negatively influenced by other systems and sources of interference The readers can still disturb each other at a distance of approx two to three times the reading distance High energy sources of interference in the range of the modulation and carrier frequencies can also interfere with the transmission 2 1 1 Mechanical structure of the flush mount version 2 1 2 Mechanical structure of th...

Page 16: ...ms is partially pulsed short term voltage drops cannot be detected with a conventional multimeter digital or analog However these voltage drops can cause a POWER ON RESET on the reader component which can lead to communication problems When dimensioning the power supply and the cable cross sections of the cabling the maximum current consumption must be taken into account It is essential to ensure ...

Page 17: ...ing to this graphic 6 5 8 7 4 3 2 1 i Notice The wiring must be carried out in a de energized state In other words the operating voltage may only be switched on after the reader has been fully installed Connection terminal ST1 8 pin screw plug terminal voltage supply interfaces PIN number Description 1 RS485 data A 2 RS485 data B 3 Do not connect 4 Do not connect 5 Do not connect 6 Do not connect ...

Page 18: ...curity Systems B V 2 4 Assembling the reader Flush mount version 1 Use the provided screws to screw the wall bracket onto a DIN device socket with a device screw distance of 60 mm 2 Support the reader s tear detection by fixing the perforated tear off tab with an additional locking screw ...

Page 19: ...stallation manual 2021 02 01 F 01U 389 837 Surface mount version 1 Screw the wall mount frame to the wall using the screws The connection cable can be inserted from above below or directly from the wall 2 Tear detection is supported by fixing the upper left screw ...

Page 20: ...der has 6 DIP switches Each switch is numbered from 1 to 6 With the DIP switches it possible to Set the address of the reader Set the BUS termination Set baud rate for phg_crypt protocol To change the reader configuration 1 Power off the reader 2 Set the DIP switches correctly 3 Power on the reader 6 5 4 3 2 1 6 5 8 7 4 3 2 1 ON WE OSDP protocol Address 1 2 3 4 5 6 7 8 S1 ON ON ON ON S2 ON ON ON O...

Page 21: ...s S1 to S4 set to OFF 2 5 2 Connecting and mounting the reader module 1 Insert the wired connection terminal on the reader module 2 Place the reader module flat on the wall bracket Push the connection cable with the reader module back into the flush mounted box 3 Push the attached reader module down until the reader module clicks into place on the wall bracket 4 After it has successfully clicked i...

Page 22: ...ctory each reader is set to the OSDP installation mode to active When operating a reader with an AMC using OSDP secure channel a dedicated generated encryption key secures operation and prevents the use of the reader in a different site Should it be necessary to change the connection to another access modular controller then the OSDP key must be reset It is necessary to reset the OSDP key if reade...

Page 23: ...objects rings fingernails keys etc 2 For cleaning do not use any corrosive or plastic corrosive liquids such as gasoline turpentine nitrous solution etc Harsh detergents can damage or discolor the surface 3 Do not use cleaning agents with mechanical effects such as scouring milk scouring sponge etc 4 Only clean the reader with a soft damp cloth and only use clear water ...

Page 24: ...ronmental Usage indoor outdoor Operating temperature C 25 C to 60 C Operating temperature F 13 F to 140 F Degree of protection IEC 60529 IP54 Electrical Operating voltage VDC 8 VDC to 30 VDC Power consumption VA 3 5 VA maximum 2 5 VA typically Operation Audible indication yes Credential type Card PIN Keyfob Keypad yes no Optical indication yes Software compatibility Building Integration System BIS...

Page 25: ...LECTUS select Technical specifications en 25 Bosch Security Systems B V Installation manual 2021 02 01 F 01U 389 837 Connectivity Reader interfaces RS485 Protocol OSDP phg_crypt ...

Page 26: ...odes and refer to the serial number on the product label Support Access our support services at www boschsecurity com xc en support Bosch Security and Safety Systems offers support in these areas Apps Tools Building Information Modeling Commissioning Warranty Troubleshooting Repair Exchange Product Security Bosch Building Technologies Academy Visit the Bosch Building Technologies Academy website a...

Page 27: ...LECTUS select More information 27 Bosch Security Systems B V Installation manual 2021 02 01 F 01U 389 837 ...

Page 28: ...28 More information LECTUS select 2021 02 01 F 01U 389 837 Installation manual Bosch Security Systems B V ...

Page 29: ......

Page 30: ...Bosch Security Systems B V Torenallee 49 5617 BA Eindhoven Netherlands www boschsecurity com Bosch Security Systems B V 2021 202103121242 ...

Reviews: