background image

2  | LBB 1990/00 Plena Voice Alarm Controller

Each message can have any length within the total
available capacity. Messages and configurations are
uploaded from a PC via USB into the memory, after
which the unit operates without PC connection. The
standard WAV-format is used for the messages and
sample rates of 8 kHz up to 24 kHz with 16-bit word
length (linear PCM) are supported. This gives up to 17
minutes of recording time with CD-quality signal-to-
noise ratio.
The unit has 12 contact trigger inputs for business and
emergency (EMG) calls. Each can be configured for a
message consisting of a sequence of up to 8 wave files.
In this way some wave files may be used in different
combinations with other messages, optimizing flexibility
and used storage space. Multiple messages can be
merged to form one integrated message. Together with
this sequence, for each trigger input, a zone selection
can be configured.

Certifications and Approvals

EMC emission

acc. to EN 55103-1

EVAC compliance

acc. to IEC 60849

EMC immunity

acc. to EN 55103-2

Safety

acc. to EN 60065

Installation/Configuration Notes

Rear view

Parts Included

Quantity Component
1

LBB 1990/00 Plena Voice Alarm Controller

2

19”Mounting brackets

1

Mains cable

1

Plena CD

Technical Specifications

Electrical

Mains Voltage

230 / 115 VAC, ±10%, 50 / 60 Hz

Main Power Consumption

60 VA

Max/Rated Output Power

360 W / 240 W

Battery Current

24VDC, +20% / -10%

Max Mains Inrush Current

8A @ 230 VAC / 16A @ 115 VAC

Mains Current
System Idle

0.26 A = 60 VA

System Idle with Pilot Tone

0.6 A = 136 VA

Maximum Load*

)

3.6 A = 830 VA

24 V Current
System Idle

0.9 A

Maximum Load*

14 A

Performance
Frequency Response

60 Hz – 18 kHz (+1/-3 dB, @ -10 dB ref. rated
output)

Distortion

<1% @ rated output, 1 kHz

Bass Control

-8/+8 dB @ 100 Hz

Treble Control

-8/+8 dB @ 10 kHz

Inputs Mic / Line
Input Type

XLR, 6.3 mm jack

Sensitivity

1 mV / 1V

S/N

63 dB (flat at max volume)

S/N

75 dB (flat at min volume/muted)

Headroom

25 dB

Speech Filter

-3 dB@ 315 Hz, high-pass, 6 dB/oct

Phantom Power Supply

12 V

VOX Trigger Level

–20 dB (100   V mic / 100 mV line) 
or via input contact

Limiter

Automatic

BGM and PC Call Station
Input Type

Cinch stereo (converted to mono)

Input Level

200 mV – 2 V

Impedance

22 kOhm

S/N

70 dB (flat at max volume)

S/N

75 dB (flat at min volume/muted)

Headroom

25 dB

Trigger Inputs

6 EMG, 6 business

Type

MC1,5/14-ST-3,5

Activation

Programmable

Supervision

On EMG inputs, programmable

Supervision Method

Series / parallel resistor

100 V Input

MSTB 2,5 /16-ST

Power Handling Capacity

480 Watts

*) Maximum load means; maximum power out, maximum load 24V out, maximum number of

call stations