GPRS/GSM IP Communicator
Troubleshooting | en
47
Bosch Security Systems, Inc.
Installation and Operation Guide
F01U163066 | 01 | 2010.05
7.2.11
Firmware Upgrade In Process
Description:
The ITS-DX4020-G is actively replacing the current firmware with the newly received firmware.
Do not power the module off during this phase, or the module might become permanently
damaged.
Solution:
1.
If power was removed during the firmware upgrade process, attempt to upgrade the
firmware as described in
Section 6 Firmware Upgrade, page 35
.
2.
If the firmware upgrade is not possible, replace the ITS-DX4020-G.
7.2.12
No Incoming IP Packets
Description:
A GPRS IP address was obtained, but no reply packets from the central station or RPS have
been received. The ITS-DX4020-G has a valid data connection with the wireless service
provider, but did not receive communication from the destination address.
Solution:
Initiate communication from the control panel and wait 5 min. Then, perform the following
tasks:
–
ITS-DX4020-G:
–
Check that the correct GPRS Access Point Name (APN) has been entered. Make sure
there are no spaces in the APN. If you are unsure, re-enter the APN.
–
If you are using AES encryption, verify that your key matches the receiver’s key.
–
Control Panel:
–
If your control panel is not using polling (polling = 0), generate an event to verify
operation.
–
Verify that the correct central station receiver IP address and port number are set.
–
Check other specific control panel communication programming options.
–
D6600 or D6100i Communication Receiver/Gateway:
–
Verify that the account is set up correctly in the receiver.
–
If the account is set up, verify communications is enabled and resynchronize the
account to make sure the control panel has the correct anti-substitution key.
–
If this is the first installation (account at the receiver or if all accounts failed), check
the network firewall.
–
Wireless Service Provider:
–
Verify with the wireless service provider that a network outage did not occur.
–
Verify that the wireless service provider’s network firewall setup is correct.
7.2.13
Control Panel Bus Problem
Description:
The control panel bus was not detected at power up, or the unit is programmed for GSM
(PSTN) mode and has detected the control panel bus wiring is connected to a device. This
state only lasts 30 sec, and then changes to a double flash.
Solution:
1.
Check for complete bus wiring to the control panel. Refer to
2.
If in GSM mode, make sure the data bus wires are not connected or touching any metal
surfaces.