background image

ISN-CP1-CM-W50, ISN-CP1-CM-N100

 | Installation Instructions | 5.0   Troubleshooting Guide 

 

 

Bosch Security Systems | 8/05 | 4998154997B 

 

5.0   Troubleshooting Guide 

Table 4:  Detector Troubleshooting 

 

Symptom Probable 

Cause 

Solution 

No alarm or the Alarm LED never 
lights 

No power 

Damaged wires 

Improper connection 

Insulation problem 

Turn the power ON. 

Change the wires. 

Tighten the screws to improve the connection. 

 

Object in the coverage pattern 

Remove the object. 

Adjust the coverage pattern. 

 

Alarm LED does not light.  

Turn DIP Switch 1-1 to ON. 

The unit only detects occasionally 

The intruder does not cross the 
detector’s field of view. 

Adjust the coverage pattern so that the 
intruder crosses the field of view. 

False alarms 

The detector is installed too close to a 
source of electromagnetic noise or is 
wired too close to a power source. 

Relocate the detector. 

Reroute the wiring. 

 

Sudden temperature fluctuation 

Exposed to direct sunlight 

Remove the heat source. 

Readjust the coverage. 

Block the light with blinds. 

 

The detector body is not attached to 
the base. 

Attach the detector body firmly on the base. 

Alarm LED lights but there is no 
alarm output 

Controller not armed 

Arm the controller. 

Tighten the screws to improve the connection. 

 

Damaged wires 

Improper connection 

Insulation problem 

Check with a tester. 

Tighten the screws to improve the connection. 

  When Form 1B (NC) is used, the alarm 

output is connected in parallel with the 
outputs from other detectors. 

Connect in series with the other detector’s 
output. 

Wire only one detector per loop. 

Alarm LED flashes (one per 
second). 

The detector activates self diagnosis 
due to mechanical failure. 

Replace the detector. 

Relays operate in reverse. 

The relay setting is reversed. 

Change the position of DIP Switch 1-2. 

 

Summary of Contents for ISN-CP1-CM-W50

Page 1: ...EN Installation Instructions PIR Detector ISN CP1 CM W50 ISN CP1 CM N100 ...

Page 2: ...por or high humidity that can cause condensation Mount the detector on 2 5 m 8 2 ft to 5 m 16 4 ft ceilings Install the detector so that intruders cross the coverage pattern Do not install the detector where pets are present Avoid installing the detector where cabinet doors curtains or other objects that can swing or move are within the coverage pattern 2 0 Installation Do not apply power until af...

Page 3: ...s 7 Spare No connection Refer to Table 2 to determine the minimum gauge wire required between the power source and the detector The table is based on one detector connected to a 12 VDC power source Table 2 Wiring Specifications Wire Gauge Maximum Length 0 3 mm2 AWG 22 700 m 2250 ft 0 5 mm 2 AWG 20 1200 m 3900 ft 0 75 mm2 AWG 18 1800 m 5900 ft When adding two or more detectors to a wire run the max...

Page 4: ... pyro sensor or the amplifier The Alarm output operates when this fault condition occurs 2 For UL Certificated installations you must set the sensitivity to 100 or 120 You must set the pulse count to 1 3 The detector activates an alarm when the count reaches the number of specified pulses within an interval of 10 sec or less The unit resets the count 10 sec after the last pulse As a guide set a pu...

Page 5: ...ft 46 ft 0 m 2 m 4 m 6 m 8 m 10 m 12 m 14 m 46 ft 39 5 ft 33 ft 26 5 ft 20 ft 13 ft 6 5 ft 0 ft 1 60 0 m 2 5 m 0 ft 8 ft 0 m 5 m 10 m 14 m 0 ft 33 ft 46 ft 2 16 5 ft 1 Top view 2 Side view Figure 6 ISN CP1 CM N100 Coverage Patterns 0 m 5 m 10 m 15 m 20 m 25 m 30 m 0 ft 16 5 ft 33 ft 49 ft 65 5 ft 82 ft 98 5 ft 0 m 2 8 m 0 ft 9 2 ft 1 0 m 5 m 10 m 15 m 20 m 25 m 30 m 0 ft 16 5 ft 33 ft 49 ft 65 5 f...

Page 6: ...magnetic noise or is wired too close to a power source Relocate the detector Reroute the wiring Sudden temperature fluctuation Exposed to direct sunlight Remove the heat source Readjust the coverage Block the light with blinds The detector body is not attached to the base Attach the detector body firmly on the base Alarm LED lights but there is no alarm output Controller not armed Arm the controll...

Page 7: ...rating Temperature and Humidity 20º C 4º F to 50º C 122º F 95 RH or less non condensing Alarm Contacts One selectable Form 1A NO or 1B NC semiconductor relay 0 1 A at 30 VDC Tamper Contacts One Form 1B NC 0 1 A at 30 VDC Alarm LED Indication Red Flashes when power is first applied and when the detector initiates self diagnosis Lights when the detector activates an alarm Mirror Angle Adjustment 30º...

Page 8: ... 2005 Bosch Security Systems 4998154997B Bosch Security Systems 130 Perinton Parkway Fairport NY 14450 9199 Customer Service 800 289 0096 Technical Support 888 886 6189 ...

Reviews: