en | Wiring
Photobeam 5000
Wiring distance
Refer to the table to determine the minimum wire gauge for a single sensor system (one
transmitter and one receiver). The distances specified are between the power source and the
last (farthest) unit on the single wire run. For multiple detector configurations, divide the wire
distance in the table by the number of systems in the configuration (1 system = 1 transmitter
and 1 receiver).
Wire Gauge
Maximum wiring distance
ISC-FPB1-W60QF
ISC-FPB1-W120QF
ISC-FPB1-W200QF
AWG
Ø mm 12V
24V
12V
24V
12V
24V
22
0.65
90 m
(295 ft)
820 m
(2690 ft)
80 m
(262 ft)
790 m
(2591 ft)
80 m
(262 ft)
770 m
(2526 ft)
19
0.90
170 m
(557 ft)
1600 m
(5249 ft)
170 m
(557 ft)
1550 m
(5085 ft)
160 m
(524 ft)
1500 m
(4921 ft)
16
1.29
320 m
(1049 ft)
2930 m
(9612 ft)
310 m
(1017 ft)
2830 m
(9284 ft)
300 m
(984 ft)
2740 m
(8989 ft)
Wiring routes
Refer to the graphics below for wiring routes examples. The illustrations depict both one, and
two sets of detector systems on a single wire run.
The graphics below show simple examples of wiring concepts, depicting how to power the
transmitter and receiver pairs, and how to combine alarm outputs. Local regulatory
requirements and technical parameters specific to a connected control panel determine the
exact details of the wiring. Review local regulations and the connected control panels
technical documentation before planning wire routes and connections. Selecting the proper
wire routes and gauges depend on the number of devices, overall distance, and voltage drop
parameters for each individual device.