6 720 680 226
10
Installation instructions
3.3.1
Vent material
All combustion air and vent pipe materials and fittings
must comply with the following:
For specific questions concerning vent material,
specifications, usage or installation, please
contact the vent manufacturer directly.
All vent connections must be glued, except for the
exhaust accessory (see section 3.3.4) which is
screwed into place on the top of the appliance. Slide
the vent pipe into the exhaust accessory. The exhaust
pipe must be properly supported and must be pitched
a minimum of a ¼ inch per foot back to the appliance.
This allows the condensate to drain properly.
An optional concentric vent/air intake termination can
be used for the installation of a vertical or horizontal
venting system. (see Fig. 8).
The concentric vent/air intake body can be ordered
from your local wholesaler. (Part# 196016).
The appliance can also be installed with separate air
intake and exhaust piping (see Fig. 11, Fig. 17 and Fig.
18, page 16).
Fig. 8
Concentric vent kit example
Item
Material
United States
Canada
Vent or
air pipe
and
fitting
PVC schedule 40
ANSI/ASTM D1785
CSA or ULC
certified only
(ULC-S636)
PVC-DWV
ANSI/ASTM D2665
CPVC schedule 40
ANSI/ASTM F441
ABS-DWV schedule 40 ANSI/ASTM D2661
Pipe
cement /
primer
PVC
ANSI/ASTM D2564
CPVC
ANSI/ASTM F493
ABS
ANSI/ASTM D2235
Table 2 Approved vent material
i
Do not use cellular foam core pipe.
Description
Length
Kit part no.
and quantity
196016
3- In. Rain Cap
N/A
1
4- In. Diameter
SDR-26 Pipe
24 In. long
1
3- In. Y
Concentric Fitting
N/A
1
2- ½ In. Diameter
SDR-26 Pipe
37-1/8 in. long
1
3- In. Termination
Tee (part #
196061)
N/A
1
3x3x1.5- In Con-
densate drain bush-
ing (part# 196278)
N/A
1
Table 3 Concentric vent part breakdown
6720608836-27.1Av
3 (76mm)
"
3 (76mm)
"
INTAKE
EXHAUST
COMBUSTION
AIR
MAINTAIN 12 IN. (18 IN. FOR CANADA)
MINIMUM CLEARANCE ABOVE
HIGHEST ANTICIPATED SNOW LEVEL.
MAXIMUM OF 24 IN. ABOVE ROOF.
EXHAUST
ROOF BOOT/
FLASHING (FIELD
SUPPLIED
DRAIN TEE
(196278)
CONCENTRIC
VENT KIT
(196016)