Bosch HPC 410 Installation Instructions For Contractors Download Page 4

Product information

 

HPC 410 – 6721832682 (2021/02)

4

2

Product information

This is an original manual. This manual may not be translated without the 
approval of the manufacturer.

2.1

Declaration of conformity

The design and operating characteristics of this product comply with the 
European and national requirements.

The CE marking declares that the product complies with all the 
applicable EU legislation, which is stipulated by attaching this 
marking.

The complete text of the Declaration of Conformity is available on the 
Internet: worcester-bosch.co.uk

2.2

Product Description

The user interface HPC 410 controls max. 4 heating/cooling

1)

 circuits 

individually and a cylinder primary circuit for DHW heating, solar DHW 
heating and solar central heating backup.

• The user interface incorporates a time program:

– Heating systems: For each heating circuit, 2 time programs with 2 

switching times per day.

– Domestic hot water: One time program for DHW heating and one 

time program for the DHW circulation pump, each with 6 
switching times per day.

• Certain menu items are specific to certain countries and are only 

displayed if the country in which the heat pump is installed has been 
set accordingly.

The functional scope and thus the menu structure of the user interface 
are determined by the structure of the system. The adjustment ranges, 
default settings and functional scope may differ from the information in 
these instructions, depending on the system installed at the site. 

Depending on the software version of the control unit, the texts shown in 
the display may differ from the texts in this manual.

• If 2 or more heating/cooling

1)

 circuits are installed, settings for each 

heating/cooling

1)

 circuit is available and are necessary.

• If special system components and modules are installed (e.g. 

MS 200 solar module, pool module MP 100), corresponding settings 
are available and necessary.

Control modes

The following main control modes are available for the heating system:

Outdoor-temp.-compensated

– the flow temperature is adjusted based on the outside 

temperature according to an optimised heating curve.

Outdoor-temp.-compensated with low end

– the flow temperature is adjusted based on the outside 

temperature according to a simplified heating curve.

For both of the control modes a room controller may be installed in the 
reference room to allow the influence of the measured and required 
room temperature. The heating curve is then adjusted accordingly.

If cooling is active, a set constant temperature is maintained.

2.3

Additional accessories

Function modules and user interfaces of the EMS 2 control system:

User interface CR10

2)

 as a simple remote room controller.

User interface CR10H

 as a simple remote room controller with 

option to measure relative humidity (heating/cooling circuits).

MM 100

: module for one heating/cooling circuit with mixing valve.

MP 100

2)

: module for a swimming pool.

MS 100

2)

: module for solar DHW heating.

MS 200

2)

: module for advanced solar systems.

Combination is not possible

 with the following products:

• FR..., FW..., TF..., TR..., TA...

3

Commissioning

WARNING

Risk of scalding!

As DHW temperatures above 60 °C can be reached when the customer 
activates the extra DHW function, a temperature mixing device must be 
installed.

NOTICE

Floor damage!

The floor may be damaged due to excessive heat.

▶ For underfloor heating systems, make sure that the maximum 

temperature for the floor type in question is not exceeded.

▶ If necessary, connect an additional temperature switch at the voltage 

input of the respective circulation pump and to one of the external 
inputs.

3.1

General commissioning of the user interface

1. Do proper coding of the modules (observe instructions of the 

modules).

2. Switch on the system.
3. Commission the remote room control (observe the operating 

instructions of the remote room control).

4. Once the user interface HPC 410 is connected to the power supply, 

the 

Language

 menu appears on the display. Make adjustments by 

turning and pressing the selector.

5. Set the language.

The display changes to the 

Date

 menu.

6. Set the date and confirm with 

Next

.

The display changes to the 

Time

 menu.

7. Set the time and confirm with 

Next

.

The display changes to the 

Country information

 menu.

8. Set the country and confirm.

The display changes to the 

Buffer cyl.

 menu.

9. Select 

Yes

 if a buffer cylinder is installed and confirm. Otherwise 

select 

No

 and confirm

3)

.

The display changes to the 

Configuration wizard

 menu.

10.Start the configuration wizard with 

Yes

 (or skip with 

No

).

11.Check and, if necessary, adjust the settings in the service menu and 

perform configuration of specific modules (e.g. solar).

12.Remedy warning and fault displays, if necessary, and reset fault 

history.

13.Name heating circuits (

 operating instructions).

14.System handover (

Chapter 3.6).

3.2

System commissioning with the configuration wizard

The configuration wizard automatically recognises which BUS nodes are 
installed in the system. The configuration wizard adjusts the menu and 
the factory defaults.

The system analysis may take up to one minute.

After the configuration wizard has performed the system analysis, the 

Commissioning

 menu is opened. The sub-menus and settings must 

1) Cooling mode is not available in BE and DK.

2) This accessory is not available in IE and UK. 

3) The buffer cylider option is not available for Air/Water indoor units with 

integrated buffer cylinder (AWMB).

Summary of Contents for HPC 410

Page 1: ...6721832682 2021 02 Installation instructions for contractors User interface HPC 410 EMS 2 0010031776 002 ...

Page 2: ...s for the heat pump 6 4 1 1 Menu Heat pump 6 4 1 2 Menu Pumps 7 4 1 3 Menu External connections 7 4 1 4 Menu Smart grid 8 4 1 5 Menu PV system 8 4 2 Additional heater settings 8 4 2 1 Menu Set additional heater 8 4 2 2 Menu Electric auxiliary heater 8 4 2 3 Menu Auxiliary heater with mixer 9 4 3 Heating settings 9 4 3 1 System data 9 4 3 2 Menu Priority heating circuit 1 10 4 3 3 Menu heating circ...

Page 3: ...CE NOTICE indicates that material damage may occur Important information Theinfosymbolindicatesimportantinformationwherethereisnoriskto people or property 1 2 General safety instructions H Notice for the target group These installation instructions are intended for plumbers heating engineers and electricians All instructions must be observed Failure to comply with instructions may result in materi...

Page 4: ...2 control system User interface CR102 as a simple remote room controller User interface CR10H as a simple remote room controller with option to measure relative humidity heating cooling circuits MM 100 module for one heating cooling circuit with mixing valve MP 1002 module for a swimming pool MS 1002 module for solar DHW heating MS 2002 module for advanced solar systems Combination is not possible...

Page 5: ...d confirm Mixer heating circuit 1 Yes No setting that defines whether heating circuit 1 is a heating circuit with mixer Mixer runtime heat circ 1 0 600 s setting that specifies the time required by the mixing valve in heating circuit 1 to turn from one stop to the other Heating system heat circ 1 Radiators Convector Floor setting for the type of heating distribution in the selected heating circuit...

Page 6: ... system Press and hold the selector until a pop up menu is displayed Select Yes in the menu Switch from standby mode to normal operation To permanently shutdown Disconnectpower from the entire system and all BUS nodes After a prolonged power failure or extended period of idleness the date and time may need to be reset All other settings are retained permanently 3 8 Quick start of heat pump Open th...

Page 7: ...rt time for the low noise operation Low noise operation until set the stop time for the low noise operation Min outside temp Below this outdoor temperature the heat pump switches over to normal operation Menu item Control range Function description Prim heating pump mode Automatic The primary circulation pump is in operation when any heat source is active When all heat sources are off the circulat...

Page 8: ... increased DHW peak The energy available in the PV system is used for DHW Yes No If enabled the DHW is heated to the temperature set for DHWoperatingmode DHWcomfort Noheatingisdoneif the holiday program is active Cooling setback mode If Onlycoolwith PV is setto Yes sethowmany degrees the heat pump is allowed to lower the indoor temperature Only cool with PV Cooling mode is activated only if energy...

Page 9: ... heater is allowed to start and the heat pump is blocked below the set outdoor temperature Alternating operation Bival pt switch mode2 Add heater DHW cylinder Yes No Choose if the DHW cylinder has an electric additional heater installed Menu item Control range Function description Is a buffer cylinder installed Yes No Set if a buffer cylinder is installed in the heating system Config HC1 at HP No ...

Page 10: ...automatically changes from the setback mode to the heating mode Heat constantly below a certain outside temperature Frost prot Notice to ensure frost protection for the entire heating system set outside temperature dependent frost protection This setting is independent of the set control type Outdoor temp Room Room and outside temp frost protection is deactivated activated on the basis of the temp...

Page 11: ...etectionisdeactivatedfortheselected heating circuit Menu item Adjustment range Design temperature or End point 30 75 85 C radiator convector 30 45 85 C underfloor heating system The design temperature is only available with weather compensated control without base point The design temperature is the flow temperature that is reached at the minimum outside temperature and therefore affects the steep...

Page 12: ... protection outside temperature threshold is set It is only effective if Frost prot Outdoor temp or Room and outside temp is set in the menu NOTICE Domestichotwatercarryingpartsmaybedamagedbeyondrepairif thefrostprotectionlimittemperatureissettoolowandinprolonged periods with outside temperature below 0 C Only contractors are permitted to adjust the factory setting of the frost protection limit te...

Page 13: ...ase Fig 6 2 Holding phase period 1 7 99 days time delay between the beginning of the holding phase duration of the maximum temperature for screed drying and the next phase Fig 6 4 Holding phase temp 20 55 C flow temperature during the holding phase maximum temperature Fig 6 4 Cool down phase incr No cool down phase no cooling phase takes place 1 10 days setting for the time delay between the steps...

Page 14: ...ed by the heat source Circulation oper mode Off circulation off On circulation permanently on by taking the start frequency into account As DHW system Activate the same time program for circulation as for DHW heating Further information and settingsofthecustomisedtimeprogram userinterface operating instructions Own time program activate customised time program for circulation Further information a...

Page 15: ...r 3 minutes as soon as there is a short tap 2 10 seconds The pump is then blocked for 10 minutes Automat therm disinfect Yes the thermal disinfection is started automatically at the set time No the thermal disinfection is not started automatically Therm disinfection day Monday Tuesday Sunday weekday on which thermal disinfection is performed Daily heat up thermal disinfection is performed daily Th...

Page 16: ...in the system can be called up in this menu 4 9 6 Maintenance menu The contact address for a service company can be set in this menu The contactaddress is automatically displayed to the end user in case of a fault Entering company name and telephone number The current cursor position will flash marked by Turn the selector to move the cursor Press the selector to activate the input field Turn and p...

Page 17: ...rvice providers and or Bosch affiliated enterprises In some cases but only if appropriate data protection is ensured personal data might be transferred to recipients located outside of the European Economic Area Further information are provided on request You can contact our Data Protection Officer under Data Protection Officer Information Security and Privacy C ISP Robert Bosch GmbH Postfach 30 0...

Page 18: ...ture sensor in the controller in accordance with table If the sensor values matched but the voltage values do not match replace the control unit A01 811 and A41 4051 4052 DHW provision thermal disinfection unsuccessful Test procedure Cause Action A11 1038 Invalid time date Test procedure Cause Action Date time not yet set Set date time Prolonged loss of power supply Avoid voltage failures A11 3061...

Page 19: ...ion Check parameter settings at the installation level Register room temperature dependent controller for heating circuit 1 4 as remote control Hxx Test procedure Cause Action For instance service interval of heat source elapsed Service required see documents for the heat source A01 5378 Outdoor unit defrost failure Test procedure Cause Action Too low temperature of heating system Open more thermo...

Page 20: ...ogic ext connection 1 Block compr operation Block HW operation Block heating mode Block cooling mode Overheat protection HC1 ESC blocking time1 on ESC blocking time2 on ESC blocking time3 on Block additional heater PV system External connection 2 External connection 3 External connection 4 Fuse size Manual defrosting Smart grid Heating Selectable peak Forced peak DHW Selectable peak PV system Heat...

Page 21: ... dry System Screed drying system Screed dry HC 1 4 Screed drying heating circuit 1 4 Start Interrupt Continue DHW settings DHW operation energy manager Switch on temp EM Switch off temperature EM DHW comfort Switch on temperature Switch off temperature Ramp up delay DHW Eco Switch on temperature Switch off temperature Ramp up delay DHW Eco Switch on temperature Switch off temperature Ramp up delay...

Page 22: ...ion Start Time Save all settings Commissioning complete Diagnosis Function check Activating function checks Heat pump Heating circuit 1 4 DHW settings Ventilation Pool Solar Monit values Heat pump Heating circuit 1 4 DHW settings Ventilation Pool Solar Output limiter Fault displays System information Maintenance Reset Calibration SnapShot ...

Page 23: ......

Page 24: ... Cotswold Way Warndon Worcester WR4 9SW United Kingdom Tel 0330 123 9559 worcester bosch co uk 0330 123 3366 TECHNICAL SUPPORT RENEWABLE SUPPORT 0330 123 9229 CONTROLS AND CONNECTIVITY TEAM 0330 123 3641 0330 123 9339 0330 123 9779 0330 123 9119 0330 123 0166 0330 123 9669 ...

Reviews: