▶ Touch the symbol
.
The appliance will start the auto adjustment of the
maximum gas flow.
Fig. 49
L1 gas adjust value
▶ Record the L1 gas adjustment value in table 23, after
check mark symbol appears in the display.
▶ Touch the symbol
to finish the L1 Gas adjust.
▶ Touch symbols
or
to select
P1 Max. Power
.
▶ Touch the symbol
to enter
P1
menu.
▶ Touch symbols
or
to select
A1 Air Adjust
.
▶ Touch the symbol
.
The appliance is in the position for adjustment of the
maximum Air flow.
▶ After the appliance has stabilized for 2 to 5 minutes, the
CO
2
probe should be inserted as per section 8.9.1.
▶ Touch symbols
or
until the CO
2
analyzer shows an
acceptable value as indicated in table 24.
▶ Record the A1 air adjustment and CO
2
values in the
table 23.
▶ Touch the symbol
.
▶ Touch the symbol
.
Display screen reads
P1 Max. Power
.
The adjustment of the maximum gas and air flow is
completed.
▶ Once P1 is adjusted remove CO
2
analyzer.
8.9.3 Adjusting the minimum flow (Parameter P2)
▶ Access to menu
P2
.
Appliance will ramp down to low fire and the water flow
should decrease. Wait a few minutes until stabilize.
▶ Touch symbols
or
to select
U2 - L2 Auto Adjust
.
▶ Touch the symbol
.
The appliance will start the auto adjustment of the
minimum gas flow.
Fig. 50
L2 gas adjust value
▶ Record the L2 gas adjust value in table 23, after check
mark symbol appears in the display.
▶ Touch the symbol
to finish the L2 Gas adjust.
▶ Touch symbols
or
to select
P2 Min. Power
.
▶ Touch the symbol
to enter
P2
menu.
▶ Touch symbols
or
to select
A2 Air Adjust
.
▶ Touch the symbol
.
The appliance is in the position for adjustment of the
minimum Air flow.
▶ After the appliance has stabilized for 2 to 5 minutes, the
CO
2
probe should be inserted as per section 8.9.1.
▶ Touch symbols
or
until the CO2 analyzer shows
an acceptable value as indicated in table 24.
▶ Record the A2 air adjustment and CO
2
values in the
table 23.
▶ Touch the symbol
.
▶ Touch the symbol
.
Display screen reads
P2 Min. Power
.
The adjustment of the minimum gas and air flow is
completed.
The auto adjust process takes several
minutes.
▶ Do not interfere with the appliance
during the auto adjustment process.
After adjusting parameter
P1
and to avoid
damaging the CO
2
analyzer by removing the
probe before measuring and adjusting
parameter
P2
.
The auto adjust process takes several
minutes.
▶ Do not interfere with the appliance
during the auto adjustment process.