6 720 816 815 (2016/10)
Greentherm 9800 SE 160/199 | SEC 199
10 | Appliance details
3.3
Unpacking the heater
The heater is default-set by the manufacturer to operate with
Natural Gas, for use with Liquid Propane, follow the conversion
instructions in section 6.9.1.
Before commissioning the unit
be certain you have the heater correctly set for your type of
Gas - Propane or Natural Gas.
Identification labels are found
on the shipping box, and on the rating plate which is located on
the right side panel of the cover.
Fig. 2
Rating plate
[A]
Serial number
[B] Type of gas (Natural gas by default)
3.3.1 The box includes
•
Water Heater
•
LP Conversion Kit
•
Pressure relief valve
•
Bracket and screws for wall hanging the heater
•
Installation manual (manual can be downloaded at
www.boschheatingandcooling.com)
The Greentherm 9800 SE / SEC are not approved or
designed for:
•
Manufactured (mobile) homes, boats or any mobile
installation. (Modular homes are acceptable for
installation).
•
Use above 10500 ft A.S.L. altitude.
•
Applications where inlet water temperature is higher
than 140 °F (60 °C) for Residential appliances or 160 °F
(71 °C) for Commercial appliances.
In these applications a 3 way valve or thermostatic
mixing valve must be installed.
•
Booster applications.
3.3.2 Remove front cover
▶ Loosen two Phillips head screws located on the bottom of
the front cover (fig. 3).
Fig. 3
Loosen two Phillips head screws
In preheated inlet water applications (i.e.
solar preheat), activation flow rate will vary
depending upon the unit set point, inlet
water temperature and the demand flow rate
thru the unit. Please consult Bosch for
further details to determine if this will
function in your application.