–
There is an x second stabilization phase for the elements in
the zone (setting Stabilize For, Stabilize for, page 36).
!
Caution!
Detectors of the FCP-320 series must not be used with
intermediate alarm storage because the detector calculates a
new standby value after the reset. This can generate an
increased alarm threshold. If there is a fire, this can thus delay
the trigger of an alarm.
Before using automatic fire detectors, find out from the
manufacturer whether they can be used for intermediate alarm
storage.
In this menu you can change the pre-set time values indicated
above.
Reset after
2
Press zone key 2. This takes you to the Delay Config
menu.
3
Press zone key 3.
This takes you to the Int Alarm Stor submenu.
1
Press zone key 1.
This takes you to the Reset After submenu.
4
1
...
Use the zone keys to set the respective delay.
–
1 1 s
–
2 5 s
–
3= 10 s (default setting)
–
4 15s
–
5 20 s
Conventional Fire Panel
System Configuration | en
43
Bosch Sicherheitssysteme GmbH
2014.06 | 7.0 | F.01U.172.980
Summary of Contents for FPC-500-2
Page 1: ...Conventional Fire Panel FPC 500 2 FPC 500 4 FPC 500 8 en Installation Guide ...
Page 2: ......
Page 81: ......