Deactivating Day Mode
Specify whether you want day mode (zones with alarm
verification start a verification time in the event of an alarm) to
be exited manually by the user or automatically at a defined
time. You can program the time in this submenu.
Notice!
Day mode must always be started manually; it is not possible to
configure an automatic start.
2
Press zone key 2. This takes you to the Delay Config
menu.
1
Press zone key 1.
This takes you to the Day Mode Off submenu.
2
1
...
Use zone keys 1 or 2.
–
1=Manual (default setting)
–
2 Automatic
If you set Day Mode Off to Automatic, you must program the
changeover time from day to night mode.
1 2 3 4 5 6 7 8
Off Time: :17:00
Confirm with
Set the time with the arrow keys and confirm using the ACK key.
Alarm Verification
Notice!
This setting only applies to zones that are programmed as alarm
verification.
Note that the delay settings are only effective in day mode. In
night mode, the alarm is triggered immediately.
4.2.1
4.2.2
40
en | System Configuration
Conventional Fire Panel
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH