Input Interface Module Type In-built
Safety Notes | en
11
Bosch Sicherheitssysteme GmbH
Installation Guide
2018.11 | 7 | F.01U.012.986
1
Safety Notes
Notice!
Installation must only be performed by authorized and specialized personnel.
Caution!
Electrostatic discharge (ESD)! Electronic components could become damaged.
Ground yourself using a wrist strap or take other suitable actions.
2
Functional description
FLM-420-I2 Input Interface Module provides three monitoring functions:
–
Monitoring a line with EOL resistor for standby or triggering (interruption/short circuit)
–
Monitoring a potential free contact for open and closed states
–
Voltage monitoring between 0 and 30 V DC.
The FLM-420-I2-W Type Wall-mount can be flush mounted in standard device boxes in
accordance with EN 60670, see graphic 3. Alternatively, it can be mounted in the FMX-IFB55-S
Interface Box Surface-mount, see graphic 4.
For connection, see graphic 1.
Description
Function
LSN: a1- | b1+ | a2- | b2+
LSN
b incoming | LSN
b outgoing
LSN-POWER: 0
V | 0V | +24V | +24V LSN power supply (support points to loop through)
LSN-SHIELD
Cable shielding (if present)
IN: IN1+ | IN1- | IN2+ | IN2-
Input
1 | Input
2
Address setting is carried out using the 8 switches and a suitable pointed object, see graphic
2.
3
Technical specifications
Inputs, independent
2
LSN input voltage
15 to 33
V
DC
Max. current consumption from LSN
10.4
mA
Cable length per input
Max. 3
m
Permissible operating temperature / storage temperature -20°C to +65°C / -25°C to +80°C
Permissible rel. humidity
<96%, non-condensing
Protection class as per IEC 60529
IP 30
Classes of equipment as per IEC 60950
III
Mechanical
Permissible wire diameter
0.6 to 2.0
mm
2
Housing material and color
ABS + PC-Blend, signal white (RAL
9003)
Dimensions (Ø
x
H)
Approx. 76mm
x
30
mm