Specifications
Power:
24VAC ± 10%, 50-60Hz, 1.4 VA of standby power consumption
(Single Class II 70VA or 100VA option available)
Physical:
Printed Circuit Board and plastic stand offs.
Environmental
Operating Range
:
-40° to 176°F (-40 °C to 80°C); 10 to 90% relative humidity, non-condensing
All
controls
are
conformal
coated for environmental protection.
Digital Outputs:
Two digital outputs relay contacts rated at 10A resistive @ 125 VAC; One dedicated for the
compressor contactor 24VAC when “ON” and one dedicated for alarm purposes dry
contact Normally Open (NO)
Inputs:
Four (4) inputs. Dedicated inputs for:
High Pressure Switch (HPC)
Low Pressure Switch (LPC)
Freeze Sensor (FREEZE) 10 K @ 77F Thermistor
Condensate Overflow Sensor (CON) 230 K +/- 15%
Compressor Call (Y) Signal
Status Indication:
Visual (LED) status of power and alarms status indication.
Protection:
Surge and transient protection circuitry.
Weight:
0.14 lbs. (0.07 Kg).
Overall
Dimensions:
4-1/4” (width) by 3-3/4” (height) by 1-3/4” (recommended panel depth).
108mm (width) by 95mm (height) by 32mm (recommended panel depth).
Listed By:
UL
Mounting Hole
Dimensions:
Four mounting holes in rectangular pattern with dimensions between them as follows:
3-3/4” (width) by 3-1/4” (height).
95mm (width) by 83 mm (height).
3