Conventional aspiration smoke detector
Technical data | en
21
Bosch Sicherheitssysteme GmbH
Quick installation guide
2020.04 | 3 | F.01U.130.927
–
Aspiration smoke detector
-20 °C to +60 °C
–
PVC pipe system
0 °C to +60 °C
–
ABS pipe system
-40 °C to +80 °C
Permissible relative humidity (non-condensing)
10 to 95%
Special features
sound power level
45 dB(A)
Max. response sensitivity (max. light obscuration)
–
DM‑TP‑50(80) Detector Module
0.5%/m (0.8%/m) *
–
DM‑TP‑10(25) Detector Module
0.1%/m (0.25%/m) *
–
DM‑TP‑01(05) Detector Module
0.015%/m (0.05%/m) *
Life cycle of the fan (12 V)
43,000 hrs at 24 °C
* The sensitivity value is based on measurements with standard test fires (old value in
brackets).