6 720 818 731 (2016/07)
Tronic 4000 T | Tronic 6000 T
8 | Installation
5.2
Selecting the installation location
Regulations for the installation location
▶ Observe country-specific requirements.
▶ Installing the DHW cylinder at a safe clearance from heat
sources.
▶ Install the DHW cylinder in rooms where the temperature
does not below 0 °C.
▶ Install the DHW cylinder close to the most frequently used
hot water tap in order to reduce heat loss and wait time.
▶ Install the DHW cylinder in a room that allows the
magnesium anode to be replaced and the necessary
maintenance to be performed.
Protection zones 1 and 2
▶ Do not install in protection zones 1 and 2.
▶ Install the DHW cylinder outside of the protection zones
and maintain a clearance of 60 cm to the bathtub.
Fig. 7
Protection zones
5.3
Wall mounting bracket
Vertical installation
Fig. 8
Vertical installation
Horizontal installation (only Tronic 6000 T)
Fig. 9
Horizontal installation
CAUTION:
▶ Select a wall for mounting the cylinder that
has sufficient load bearing capacity to
support the full DHW cylinder. Page 5.
CAUTION:
▶ Make sure that the DHW cylinder is
connected by a ground conductor to the
system (fuse box).
225 cm
6 720 612 659-13.3TT
2
2
1
1
60 cm
60 cm
CAUTION:
Danger from falling device!
▶ Use screws and wall mounting brackets
suitable for the type of wall, with
specifications which permit suspension of
the full cylinder.
NOTICE:
▶ Make sure that the hot water outlet is in the
top part of the appliance.
>220
mm
<300
mm
6720812247-07.1V
D
6720812247-08.2V