![Bosch DT1 Manual Download Page 7](http://html.mh-extra.com/html/bosch/dt1/dt1_manual_50765007.webp)
7
6 720 610 367 (01.10)
1.2
Basic Settings
Channel 1 – Ch 1 – Central heating, all
days
•
ON
: 6:00
•
OFF
: 22:00.
Channel 2 – Ch 2 – Hot water, all days
(DT 2 only)
•
ON
: 5:00
•
OFF
: 22:00.
No other timed periods are pro-
grammed (
––:––
).
2
Installation
B
Switch off the central heating boiler.
B
Remove outer case if necessary.
B
Open control panel cover and
unhook if necessary.
B
Press tab (g) and remove blank
panel (h) (Fig. 2).
B
Connect connector (k) to terminal (j)
on the main circuit board (ST 5).
B
Insert timer in the space (i) and snap
into position at the top.
B
Refit the boiler components previ-
ously removed.
3
Operation
3.1
Button Functions
• Menu button
(b):
–
PROG
: Time, Day
–
Ch1 PROG
: Timed periods,
Channel 1
–
Ch2 PROG
(DT 2 only): Timed
periods, Channel 2
–
Ch1
PROG
: Mode, Channel 1
–
CH2 PROG
(DT 2 only): Mode,
Channel 2
•
(c): Clear
•
(d): Move to next setting
• Set button
(e) or
(f):
– Press and release: changes set-
ting by one unit
– Press and hold: changes setting
continuously.
Ch
C
English