10.36 Octal Relay Module Output Programming (continued)
10.36.4 Follow Zone: Program Addresses (2740-2771)
To program an Octal Relay Module for Follow Zone, follow the steps below.
1. Select Octal Relay to program.
2. Program Data Digit 1 of Program Address A as 4 for Follow Zone.
3. Program Data Digit 2 of Program Address A for the desired function.
4. Program Data Digit 1 and 2 of Program Address B for the desired zone.
Once both Address A and Address B have been programmed, proceed to program the next Octal Relay.
Octal
Relay
#
DS7488-1
Address
A
DS7488-1
Address
B
1
2
3
4
5
6
7
8
2740
2741
2742
2743
2744
2745
2746
2747
2748
2749
2750
2751
2752
2753
2754
2755
2756
2757
9
10
11
12
13
14
2758
2759
2760
2761
2762
2763
2764
2765
2766
2767
2768
2769
2770
2771
15
16
1
2
Data Digit
Program Address B
1
2
Data Digit
4
Program Address A
1
0
2
3
4
5
When panel is not Armed
When panel is Armed
When Zone is opened
When zone is shorted
Activate:
Disabled
6
SELECT OPTION DD 2
8
7
9 *0 *1 *2
Program the HEX value
of the Zone
from the chart
on the next page
Latch when activated**
** = This applies only to the DS7465 outputs.
DS7488 outputs will not latch when this is selected.