14
en | Installing the RF Fire Detection System
Radio Frequency Fire Detection System
2016.04 | 6.0 | 4.998.120.885
Operation Guide
Bosch Sicherheitssysteme GmbH
5
Installing the RF Fire Detection System
5.1
Installing the FK 100 LSN RF Interface Module
Notice!
To create a fault-free radio connection, observe the following points:
The RF interface module must not be installed in a metal cabinet.
A minimum distance of 2 m must be maintained between individual RF interface modules
installed in the same area.
Notice!
In the case of a wall-mounted configuration, fit the RF interface module in a vertical position
to ensure that the writing on the cover can still be read.
76.5
100
15
15
61.5
9
4 x
4 x
∅
6 mm
∅
4.5 x 25 mm
9
9
9
28
35
135
110
28
Figure 5.9: FK 100 LSN RF Interface Module Dimensions