D9068
|
Operation and Installation Guide | 5.0 Programming
38
Bosch Security Systems, Inc. | 3/13 | F01U071094-0
7
To program the frequency of Auto Test
Reports:
1. At the Auto Test submenu, press [2]
to select
2: TEST FREQUENCY
. The window shows:
AUTO FREQ (_)
1: 4 HOURS
2: 12 HOURS
3: 24 HOURS
4: 7 DAYS
5: 28 DAYS
6: DISABLED
This item is
currently not
supported.
The
6: DISABLED
option is not
currently supported.
2. Press the number key that corresponds
to your selection and then press [#
Command]. The revised setting appears
in parentheses on the first line.
3. After programming this feature, press
[* Clear] to return to the Auto Test
submenu.
1: TEST TIME
To access
TEST TIME
, select
[0]: PROGRAM
[1]: PROG TIME
[2]: AUTO
TEST
[1]: TEST TIME
. This option allows
you to program the time of day the Auto
Tests occur and uses a 24-h clock. For
example, enter 2300 for 11:00 p.m.
To program the time an Auto Test occurs:
1. At the Auto Test submenu, press [1]
to select
1: TEST TIME
. The window
shows:
AUTO TEST TIME
HHMM: ___________
2. Enter the time in 24-h format and
press [# Command].
3. Press [* Clear] to return to the Auto
Test submenu.
If the test frequency is not
programmed before the test
time, the first Auto Test is
not performed.
3: DAYLIGHT SAV
To access DAYLIGHT SAV, select
[0]: PROGRAM
[1]: PROG TIME
[3]:
DAYLIGHT SAV
. This option enables the
automatic adjustment of system time for
daylight saving time. The adjustment
dates are pre-programmed into the
system.
To set the system for Daylight Saving
Time:
1. At the Prog Time submenu, press [3]
to select
3: DAYLIGHT SAV
. The window
shows:
DAYLIGHT SAVING?
NO: YES (1)/NO (0)
2. The current setting precedes the
colon (:) in the second line. Press
[1] to set DAYLIGHT SAV to
Yes
. Press
[0] to set it to
No
.
3. Press [# Command] to verify your
selection.
4. After programming this feature, press
[* Clear] to return to the Prog Time
submenu.
When using the public switched
telephone network (PSTN) to
communicate, a Test Report must
be sent a minimum of once every
24 h to comply with UL and NFPA
standards.
When communicating by means
other than the PSTN, a Test
Report must be sent a minimum
of once each hour to comply
with UL and NFPA standards.
5.4.2 PROG TIMERS
The
PROG TIMERS
feature allows you to
set
time-related parameters for the AC Fail
Delay and the Display Rate.
To set time-related parameters for AC
Fail Delay and Display Rate:
At the Programming Menu, press [2] to
select
1: PROG TIME
. The window shows:
PROG TIMERS
1: AC FAIL DLY
2: DISPLAY RATE
Refer to the following sections for the
programming options.
1: AC FAIL DLY
on page 4 for
information about settings permitted in
UL864 installations.
To access
AC FAIL DLY
, select
[0]: PROGRAM
[2]: PROG TIMERS
[1]: AC
FAIL DLY
. The window shows:
AC FAIL DLY(__)
1: WAIT FOR DC
2: WAIT DLY TIME
This option sets the number of hours the
D9068 waits after an AC failure is
signaled before sending an AC Failure
Report.