D9068
|
Operation and Installation Guide | 2.0
Installation
.
Bosch Security Systems, Inc. | 3/13 | F01U071094-0
7
13
The FACPs using open collector outputs must be compatibility listed. When
installing the D9068 more than 20 ft (6 m) from the FACP, configure the
inputs for supervised operation. The D9068 can be installed up to 500 ft
(152 m) from the FACP.
2.2 Connecting the D9068
2.2.1 Input Point Connections
Remove all power before making or breaking any connections to the D9068.
Failure to do so can cause personal injury and/or damage to the
equipment.
When making connections to the D9068, refer to
on this
page through page 16.
Figure 7: Molex Connector Descriptions
+ + - - A B
1 2 3 4 5
NC C NO
KEYPAD
1
3
2
4
14
5
6
7
8
9
10
11
10
12
13
15
16
17
18
19
1 - Red (Power +)
2 - Black (Power -)
3 - TXIA
4 - RXIB
5 - White/Brown (Input Point 1)
6 - White/Red (Input Point 2)
7 - White/Orange (Input Point 3)
8 - White/Yellow (Input Point 4)
9 - White/Blue (Input Point 5)
10 - Black
11 - Red
12 - Green
13 - Yellow
14 - Terminal not used
15 - Common trouble relay
*
16 - Keypad programmer
17 - Inputs (refer to
for input specifications)
18 - Serial connection pins
19 - Power (refer to
for specifications)
* Connect the relay to an input on the FACP for trouble annunciation.
The contact position shows an off-normal condition. Under normal
operation, the trouble relay is energized. C and NO are connected.