Bosch D7212G Installation & Troubleshooting Quick Reference Manual Download Page 11

D9412G/D7412G/D7212G Installation & Troubleshooting Quick Reference Guide

D9412G/D7412G/D7212G

Page 11

© 2004 Bosch Security Systems, Inc.

43700F

Troubleshooting

3.4

Problems With Command Centers

Symptom 

Diagnosis 

Remedy 

More than one 

command center has 
the same supervised 
address. 

Use a supervised address in one command center only 

or use a different supervised address for each 
command center. 

Command centers show erratic 

behavior. For example, the pip 
that confirms you pressed a key 
echoes. 

 

Data connections 

(yellow and green 
wires) on one or 
more command 
centers are reversed, 
or only one wire is 
connected. 

Check that yellow and green data wires are correctly 

connected on all command centers. 

NO AUTHORITY

 displays at the 

command center when you enter 
your passcode to perform a 
function. 

Check the User Interface section of the program to be sure the function is 

enabled for the authority level assigned to the passcode in the Passcode 
Worksheet
 section of the program. 

Check the Passcode Worksheet section of the program to be certain the passcode 

is assigned to the area where you are attempting to perform the function. 

Check the Passcode Worksheet section of the program to see if the passcode is 

restricted by a user window. 

Check the Area Parameters section of the program to be certain the area in 

which you are attempting to perform the function is turned on. 

 

Table 6: Troubleshooting Command Center Problems

3.5

Phone Line Trouble

Phone line problems that are not corrected can result in the panel going into Communications Failure. The D9412G/D7412G
can be programmed to monitor one or two phone lines. See the D9412G/D7412G Program Entry Guide (P/N: 47775) for
programming instructions. If  the phone line monitor is enabled, 

SERVC PHONE LINE #1

 (or 

SERVC PHONE LINE

#2

 if two lines are used) appears in the command center’s display when the panel detects a problem on the phone line.

System 

Diagnosis 

Remedy 

SERVC PH LINE #1

 (or 

SERVC PH LINE #2

 if two 

lines are used) appears in the 
command center display. 

The panel’s phone line 

monitor detects a phone 
line as faulted. 

Verify that the telephone cord is correctly 

connected to the phone jack and the panel. 

Verify the Ground Start Jumper is in the correct 

position. 

If using a ground start phone line, verify a D136 

relay is correctly installed in the Ground Start Relay 
socket. 

Verify that the phone jack (RJ31X or RJ38X) is 

wired correctly. The incoming phone line must be 
wired to Terminals 4 and 5. The in-house phone 
system must be wired to Terminals 1 and 8. 

Verify that all telephones are on-hook. Leaving a 

telephone on hold after the other party hangs up 
creates an off-hook condition. Verify that no 
phones are on-hold. 

If completing the steps above does not restore the 

phone line, meter the line. You should meter at 
least 3.0 VDC. If your readings are below the 
minimum values, contact your telephone company 
repair service. 

 

Table 7: Troubleshooting Phone Line Problems

Summary of Contents for D7212G

Page 1: ...Control Panels D9412G D7412G D7212G Installation Troubleshooting Quick Reference Guide ...

Page 2: ...D9412G D7412G D7212G Installation Troubleshooting Quick Reference Guide Page 2 2004 Bosch Security Systems Inc 43700F D9412G D7412G D7212G Installation Troubleshooting Quick Reference Guide ...

Page 3: ... 8 Problems with the D8125 POPEX Data Expansion Loops 15 3 8 1 Metering the Loops 15 3 9 EMI on Long Wire Runs 16 3 10 Checking Shielded Cable 16 3 11 Battery and Power Reports 16 3 12 Watchdog Reset Reports 17 3 13 Runaway Reports to the Receiver 17 3 14 Overloaded Power Supply 17 3 15 Service Walk Test 18 3 16 Ground Fault 20 3 16 1 Procedure for Isolating Earth Ground Faults 20 3 17 Panel Buzze...

Page 4: ...gure 8 D7212G System Wiring Diagram 29 Figure 9 D7212G System Wiring Diagram 30 Figure 10 D7212G System Wiring Diagram 31 Tables Table 1 Chapter Summary 5 Table 2 Referenced Literature 5 Table 3 Quick Reference Terminal Description 7 Table 4 Troubleshooting Problems Found During Self Diagnostics 9 Table 5 Troubleshooting Problems Programming the Panel 10 Table 6 Troubleshooting Command Center Prob...

Page 5: ...are summarized in Table 1 Section No Description 1 Introduction information about organization of the manual and additional literature that may be ordered 2 Quick Reference Terminal Description description of panel terminals presented in a quick reference table 2 Basic Troubleshooting basic troubleshooting solutions and procedures to resolve common problems during programming and installation of t...

Page 6: ...138544 D7212G Program Entry Guide 4998138538 D7212G Program Record Sheet 4998138542 D7212G Release Notes 4998138543 D7412G Release Notes 43856 D8125MUX Operation and Installation Guide 36796 D9210B Operation and Installation Guide 32206 D9412G Release Notes 43821 D9412G D7412G Approved Applications Compliance Guide 43494 D9412G D7412G D7212G Installation and Troubleshooting Quick Reference Guide 4...

Page 7: ... output interrupted by RESET SENSORS or alarm verification Shares PTC with Terminals 6 and 7 D136 Plug in Relay required Install a D136 in the SW AUX socket for output at Terminal 8 9 COMMON Terminal 9 is common for Auxiliary Power Steady or Pulsed Alarm Power Alternate Alarm Power and Switched Aux Power Terminals 3 6 7 and 8 10 EARTH GROUND Connect to earth ground A cold water pipe or grounding r...

Page 8: ...D9412G D7412G D7212G Installation Troubleshooting Quick Reference Guide Page 8 2004 Bosch Security Systems Inc 43700F D9412G D7412G D7212G Quick Reference Terminal Description Notes ...

Page 9: ...C silences the buzzer The display clears when communication restores i e the receiver acknowledges a report PANEL BROKEN appears in the displays of all command centers the command center buzzer sounds and the green operation monitor LED stops flickering or is off A hardware or software problem has occurred Pressing ESC does not silence the buzzer The panel must be returned to Bosch Security System...

Page 10: ...e P N 43488 for a complete description SERVC PRINTER appears in command center displays The panel has lost contact with a supervised printer Pressing ESC silences the buzzer The displays clear when contact with the missing printer restores Table 4 cont d Troubleshooting Problems Found During Self Diagnostics 3 3 Problems Programming the Panel Before attempting to program the panel become familiar ...

Page 11: ...turned on Table 6 Troubleshooting Command Center Problems 3 5 Phone Line Trouble Phone line problems that are not corrected can result in the panel going into Communications Failure The D9412G D7412G can be programmed to monitor one or two phone lines See the D9412G D7412G Program Entry Guide P N 47775 for programming instructions If the phone line monitor is enabled SERVC PHONE LINE 1 or SERVC PH...

Page 12: ... shorted between the phone company s equipment and the receiver by placing a call to the number for the receiver If you hear the line ring but the ring detector doesn t light or if you hear a busy signal and the green on line OL indicator is not lit call the phone company for service The panel reaches a busy signal for all ten attempts to reach the receiver The receiver s call load is too great Ad...

Page 13: ...k Test to search for extra points may help diagnose the problem Problem with data expansion loop See Section 3 8 Problems with the D8125 POPEX Data Expansion Loops on page 15 Points intermittently appear as missing Points are erratic Debounce Count parameter set at 1 If an off board point is in transition between normal and faulted conditions as the panel scans it it appears as missing It is recom...

Page 14: ...the panel or Data Expansion Loop may be disconnected from POPEX module Check POPEX module for correct connections to the panel and the Data Expansion Loop If you find missing points the service walk test may help you diagnose the problem see Section 3 7 1 Extra Points Keyswitch points P Type is programmed as 4 5 6 7 or 9 report as missing If area is armed the point reports a MISSING ALARM If the a...

Page 15: ...7320 2231 14 11650 3551 Table 10 Data Expansion Loop Wire Specifications When metering the loop monitor it long enough to observe an intermittent problem To meter the data expansion loop without POPITs connected to it 1 Disconnect the loop from the POPEX Module 2 Twist the positive and then the negative wires together at each POPIT location so that the positive and negative wires are continuous to...

Page 16: ...nd source 3 10 Checking Shielded Cable If improperly installed shielded cable can create problems rather than solve them Follow the procedure below to check shielded cable for proper installation 1 Remove the drain wire for the shield from Terminal 10 2 Meter the drain wire for continuity to Terminal 10 earth ground If there is continuity find and remove the foreign ground on the drain wire 3 Reco...

Page 17: ...use runaway reports to the receiver on AC failure Be sure to replace all D8128 or D8128A OctoPOPITS with the D8128D Module 3 14 Overloaded Power Supply If the load on the panel s power supply exceeds its capacity the panel follows a routine to protect itself and the battery It sends reports to the Central Station at several points during this routine Keep in mind that AC power remains at Terminals...

Page 18: ... SERVICE WALK prompt Press ENT Or press 9 9 followed by ENT to reach the Service Menu to access the ServiceWalk Test Note TheD7412GandD7212GdoNOTincludetheServiceWalkTestintheServiceMenu Therefore theD7412Gand D7212G must have the Service Walk Test function enabled in the Function List in order for the Service Walk Test to beaccessed 3 The display shows PTS TO TEST Test the first detection device ...

Page 19: ...T ENT ESC ESC ESC ESC NEXT Test a device Test a device Test a device Test a device Text displays for 60 seconds Text displays for 60 seconds IDLE TEXT SERVICE WALK 246 PTS TO TEST POINT TEXT 245 PTS TO TEST POINT TEXT 244 PTS TO TEST POINT TEXT 1 PTS TO TEST VIEW UNTESTED 0 PTS TO TEST PTS UNTESTED POINT TEXT ESC ESC ESC Figure 1 Service Walk Test Flow Chart ...

Page 20: ... and 13 88 VDC STOP This voltage reading means that the Ground Fault may be in one of the Panel power circuits such as the Battery or AUX Remove both battery wires from terminal 4 and terminal 5 at the same time If the voltage across terminals 9 and 10 changes to 6 5 to 6 8 VDC which indicates a normal reading then the ground fault is on the battery wire or wires Locate and remove the ground fault...

Page 21: ... known earth ground is needed for the test Once the earth ground fault is isolated remove the ground repair the wire or replace the wire 6 If the voltage being read represents a ground fault on terminals 25 26 or 28 the ground fault condition may physically be on either the Zonex Bus Popit Bus or an input point on an OctoPopit or Popit To isolate the ground fault in this scenario follow these step...

Page 22: ...D9412G D7412G D7212G Installation Troubleshooting Quick Reference Guide Page 22 2004 Bosch Security Systems Inc 43700F D9412G D7412G D7212G Troubleshooting Notes ...

Page 23: ...GRAMMABLE ALARM OUTPUTS Terminals Requires Optional Model D136 Relay In ALT ALARM SW AUX 7 8 GROUND FAULT DETECT Enabled Disabled PHONE LED ON WHEN COMMUNICATING OFF WHEN IDLE GRN PROG CONN LOOP START PHONE MONITOR SELECT Point 8 GND FAULT Detect E N A B L E D I S A B L E 12 11 13 Point 1 Point 2 15 14 16 Point 3 Point 4 GROUND START Requires Relay Model D136 in Ground Start Socket GND START RED 1...

Page 24: ...EN IDLE VOLTAGE RANGES Open 3 7 5 0 VDC Normal 2 0 3 0 VDC Short 0 0 1 3 VDC GRN LOOP START PHONE MONITOR SELECT Point 8 GND FAULT Detect E N A B L E D I S A B L E 12 11 13 Point 1 Point 2 15 14 16 Point 3 Point 4 18 17 19 Point 5 Point 6 21 20 22 Point 7 Point 8 GROUND START Requires Relay Model D136 in Ground Start Socket GND START D130 1 2 5 3 4 Figure 3 D9412G System Wiring Diagram 2 of 3 1 Op...

Page 25: ... CONN Point 8 GND FAULT Detect E N A B L E D I S A B L E ZONEX OUT 2 26 25 ZONEX IN 2 ZONEX POWER 24 ZONEX COMMON 23 D8125 D8125 D8128D D8128D D8129 D8129 D9133TTL E D9131A D9210B D1260 D1257 D1256 D1255 1 1 2 5 6 7 7 8 9 10 11 3 3 3 3 3 3 3 3 3 4 Figure 4 D9412G System Wiring Diagram 3 of 3 1 Up to eight supervised D9210Bs 2 Up to three supervised D9131As 3 Power limited supervised 4 Power limite...

Page 26: ...T GND START GROUND START 12 11 13 Point 1 Point 2 15 14 16 Point 3 Point 4 GROUND START Requires Relay Model D136 in Ground Start Socket D1640 16 5 V 40 VA 60 Hzr C900 D126 Battery 12 V 7 Ah D1218 12 V 17 2 Ah or 18 0 Ah 1 2 3 4 5 8 D126 D1218 D126 D1218 D126 D1218 D126 D1218 D126 Battery 12 V 7 Ah D1218 12 V 17 2 Ah or 18 0 Ah 14 10 7 13 10 10 10 16 11 12 6 15 9 10 7 10 RJ31X Figure 5 D7412G Syst...

Page 27: ...2 0 3 0 VDC Short 0 0 1 3 VDC LOOP START GND START GROUND START 12 11 13 Point 1 Point 2 15 14 16 Point 3 Point 4 18 17 19 Point 5 Point 6 21 20 22 Point 7 Point 8 GROUND START Requires Relay Model D136 in Ground Start Socket P105BL D125B D129 P105F 2 5 3 4 D130 1 Figure 6 D7412G System Wiring Diagram 2 of 3 1 Optional For 24 V applications use a UL Listed 24 VDC Power Supply with a D130 Relay Mod...

Page 28: ...ONE LED RED ON WHEN COMMUNICATING OFF WHEN IDLE PERIPHERAL DEVICE CONNECTIONS RED POWER YELLOW DATA BUS A GREEN DATA BUS B BLACK COMMON ZONEX OUT 1 ZONEX IN 1 N F P A Style 3 5 Signaling Line Circuits LOOP START GND START GROUND START GROUND START Requires Relay Model D136 in Ground Start Socket D8125 D8128D D8129 D9133TTL E D9131A D9210B D1260 D1257 D1256 D1255 1 1 2 4 5 6 7 3 3 3 3 3 3 Figure 7 ...

Page 29: ... local AHJ connect D113 Battery Lead Supervision Module D113 BAT 2 BAT 1 BAT 2 BAT 1 SUPV CHGR CHGR VAUX D126 or D1218 D126 or D1218 To Point Input To Battery Negative To Battery Positive To AUX P PROG CONN All external connections except terminal 5 Battery Positive are inherently power limited EARTH GROUND COMMON BATTERY NEGATIVE ONLY Maximum Charging Current 1 4 Amps BATTERY POSITIVE ONLY RELAY ...

Page 30: ...All external connections except terminal 5 Battery Positive are inherently power limited EARTH GROUND COMMON BATTERY NEGATIVE ONLY Maximum Charging Current 1 4 Amps BATTERY POSITIVE ONLY RELAY A RELAY B RELAY C AUX POWER CLASS 2 TRANSFORMER 16 5 VAC 40 VA 60 Hz Model D1640 Internally Fused Do Not short Requires Unswitched Outlet Do Not Share With Other Equipment PROGRAMMABLE ALARM OUTPUTS Terminal...

Page 31: ...AY B RELAY C AUX POWER CLASS 2 TRANSFORMER 16 5 VAC 40 VA 60 Hz Model D1640 Internally Fused Do Not short Requires Unswitched Outlet Do Not Share With Other Equipment PROGRAMMABLE ALARM OUTPUTS Terminals Requires Optional Model D136 Relay In ALT ALARM SW AUX 7 8 GROUND FAULT DETECT Enabled Disabled PHONE LED RED ON WHEN COMMUNICATIN G OFF WHEN IDLE GRN PERIPHERAL DEVICE CONNECTIONS RED POWER YELLO...

Page 32: ...urity Systems Inc 43700F 09 04 130 Perinton Parkway Fairport NY 14450 9199 USA Installation and D9412G D7412G D7212G Customer Service 800 538 5807 Technical Support 888 886 6189 Troubleshooting Ref Guide Page 32 of 32 ...

Reviews: