 D5060 

  D5060 User's Guide   

© Bosch Security Systems

 B.V., 2021

 

Page 3 

F01U034899-02

 

Table 2: Point Type Entry Code 

Decimal Value 

Point Type 

Remove point from D8125MUX 

1

Contact

Sensor (or Single Point Module) 

3

I/O 

Module

Mux smoke without low temperature 

Mux smoke with low temperature 

Dual point 

5.

Press [#] to program a point connected to the
D5060 and the D8125MUX (if connected), or
press [1] to program the D8125MUX only. If the
MUX device has DIP switches, program the
device using its DIP switches.

Press [*] at any time to back up through 
the sequence. 

6.

If the point is programmed correctly, the unit
beeps once and displays 

Adr

 indicating that it is

ready to program the next point. If the point was
not programmed correctly, the unit sounds a
three-beep error tone and one of the following
messages displays:

Err: 

The point was not programmed correctly.

PnL: 

Communications with the D8125MUX
failed. 

7.

Press [*] to clear the entry, or press [#] to
reprogram.

3.3 

Removing a Point from the 
D8125MUX 

1.

Apply power to the D5060 and connect the
programmer to the D8125MUX only.

2.

Enter the address of the point you wish to
remove.

3.

When prompted for a point type, press [0]. Refer
to Table 2.

4.0 Interrogation 

Mode 

You can also use the programmer to read information 
from a D8125MUX and from MUX points. Refer to 
Section 2.0 Installation for D5060 installation 
information. 

4.1 

Reading Information from the 
D8125MUX 

1.

To put the unit into Interrogation Mode, press
and hold [7] and [9] simultaneously until the unit
beeps. The LED marked INTERROGATION
MODE lights.

2.

The display shows 

A.dr

 and the left-most

decimal point lights, prompting the user to enter a
starting address. Enter an address followed by [#].

3.

The Interrogation LED flashes. Press [#] to read
point information from the D8125MUX at that
address.

4.

Press [4] to read the previous address information
from the D8125MUX.

5.

Press [6] to read the next address information
from the D8125MUX.

If communication between the unit and the 
D8125MUX fails, the unit sounds a three-
beep error tone and displays 

PnL

6.

To exit Interrogation Mode, press and hold [*]
until the unit beeps.

4.2 

Reading Information from MUX 
Points 

Disconnect all multiplex points from the 
D8125MUX and the multiplex bus before 
reading multiplex point information. 

1.

To put the unit into Interrogation Mode, press
and hold [7] and [9] simultaneously until the unit
beeps. The LED marked INTERROGATION
MODE lights.

2.

The display reads 

A.dr

 and the left-most decimal

point lights, prompting you to enter a starting
address. Enter an address and press [#].

3.

Press 

[1].

4.

When 

t.YP

 displays at the keypad, enter the

point type of the Mux point (Table 2) and press
[#].

5.

If a point responds to the address, the
programmer beeps once and displays 

rSP

. If the

point does not respond, the unit beeps three times
and the display reads 

noP

.

6.

To exit Interrogation Mode, press and hold [*]
until the unit beeps.

Summary of Contents for D5060

Page 1: ...ded power cable to the output terminals of a 16 5 VAC transformer Insert the plug end into the jack labeled EXT POWER on the programmer Refer to Figure 2 Figure 3 and Figure 4 2 For control panels use the serial cable provided to connect the D8125MUX to the D9412G D9412 D9112 D7412G D7412 D7212G or D7212 Control Panel to the jack labeled SERIAL PORT on the programmer 3 For MUX devices without DIP ...

Page 2: ...ints 1 The D5060 displays the prompt Adr after it is powered on This indicates that it is ready to begin programming 2 If the MUX device has no DIP switches connect the D5060 to the point to be programmed Figure 2 If the MUX device has DIP switches program the device using its DIP switches The point must be connected only to the programmer and not to the D8125MUX or the MUX bus If programming poin...

Page 3: ...installation information 4 1 Reading Information from the D8125MUX 1 To put the unit into Interrogation Mode press and hold 7 and 9 simultaneously until the unit beeps The LED marked INTERROGATION MODE lights 2 The display shows A dr and the left most decimal point lights prompting the user to enter a starting address Enter an address followed by 3 The Interrogation LED flashes Press to read point...

Page 4: ... the unit displays bAd The display of Lob or bAd indicates insufficient power for programming D8125MUX communications might still function properly even if these conditions exist To preserve the life of the batteries remove them from the multiplex point programmer whenever you will not use the unit for any length of time 6 0 Specifications Table 3 Specifications Description Value Display Three dig...

Reviews: