Duct smoke housing, 2-wire
Description | en
5
Bosch Security Systems, Inc.
Installation manual
2017.04 | 7.0 | F.01U.071.685
Accessory products
D344-RT Remote test/indicator plate, 24V
D344-TF Duct tube filters, 20pcs
DRA-5 Remote indicator plate, 5V
PAM-4 Relay module, form C, 10A 12/24V
Legacy:*
D306 Remote Indicator Plate
D307 Remote Test and Indicator Plate
SMK-TM Smoke Test Magnet
* Legacy products are not available for purchase.
2.3
Setting the jumpers
For the locations of the tamper jumper and reset jumper on the power card, see the following
figure.
Figure 2.1: Jumper locations
1 Power card
2 Tamper jumper
3 Reset jumper
The tamper jumper enables or disables the housing cover tamper switch. When this jumper is
enabled, a trouble is indicated if the cover is removed. The reset Jumper enables or disables
the remote reset (D344-RT keyswitch). The power off reset from the control panel zone
functions normally regardless of the jumper setting.
Notice!
Disable the reset jumper whenever you are not using the D344-RT (D307).