Duct smoke housing, 2-wire
Specifications | en
21
Bosch Security Systems, Inc.
Installation manual
2017.04 | 7.0 | F.01U.071.685
6
Specifications
Electrical
Current (alarm)
Dependent on the control panel that must limit the alarm
current to 100 mA maximum.
Maximum RMS Ripple
25% of DC input
Power-up time
22 sec maximum
Voltage, operating
8.5 VDC to 32 VDC from two-wire loop. Optional 24 VDC/VAC
from control panel or external supply.
D340 with D344-RT, D344-RL, and External Power
Loop power
External power
8.5 V to 32 V
24 V
Condition
–
Alarm
Current limit to 100 mA
170 mA in remote test
–
Standby
< 0.120 mA
5 mA
–
Trouble
< 0.170 mA
0.030 mA
D340 with D344-RT, D344-RL without External Power
Loop power
8.5 V to 32 V
Condition
–
Alarm
Current limit to 100 mA
–
Standby
< 0.140 mA
–
Trouble
< 0.170 mA
D340 without D344-RT, D344-RL without External Power
Loop power
8.5 V to 32 V
Condition
–
Alarm
Current limit to 100 mA
–
Standby
< 0.130 mA
–
Trouble
< 0.150 mA
Environmental
Air velocity
300 ft./min to 4000 ft./min (1.5 m/s to 20.3 m/s)
Relative humidity
0% to 95%, non-condensing
Temperature, operating
+32F to +120°F (0°C to +49°C).
For UL listed requirements, the operating temperature range is
+32°F to +100°F (0°C to +37.8°C).