background image

2 | D326A Analog Point Contact Module

2. Connect the wiring: Wiring terminals are clearly marked

and the module leaves ample room in the back box for

wiring.

3. Mount the module in the back box: The D326A mounts

on a four-inch square back box.

Data Circuit Length
Data (or polling) circuit length is the distance over the
circuit wire from the connection at the FACP to the most
distant device and back to the FACP. Data circuit length
must include the distance to any device connected to the
circuit in a T tap. The screw terminals can accept up to 14
AWG (1.5 mm) wire, but this reduces the allowable length
of the circuit. Refer to the D9067 Installation Guide (P/
N: 74‑07690‑000) for specific wire instructions and
specifications.
Initiating Device Circuit Connections
The initiating device circuit can use any number of UL-listed
normally open (NO) contact closure devices. Device circuit
wiring must not exceed 50 Ω. Install contact closure devices
according to the manufacturer’s installation instructions.
All wiring must be supervised and power-limited.

Note

Do not mix fire alarm initiating and supervisory
devices on the same module.

Parts Included

Quant.

Component

1

Point contact module

1

Wall plate

1

EOL resistor, 10 kΩ

1

Hardware pack

1

Literature pack

Technical Specifications

Environmental Considerations

Operating Temperature

+32°F to +120°F (0°C to +49°C)

Mechanical Properties

Color

Ivory

Dimensions (H x W x D)

4.7  in. x 4.2  in. x 1.35 in.

(12 cm x 11 cm x 3.5 cm)

Material:

Acrylonitrile-chlorinated PE-styrene (ACS)

Response Time:

2 sec

Weight

3 oz (85 g)

Power Requirements

Current
Alarm:

28 mA

Polling:

0.022  mA ± 20%

Standby:

0.035  mA (typical)

Resistance
End of Line Device

10 kΩ, 0.25 W per resistor

Initiating Device Circuit

Less than 50 Ω

Voltage (input)
Nominal:

24 VDC

Range:

17 VDC to 41 VDC

Ordering Information

D326A Analog Point Contact Module

Allows compatible fire alarm control panels

(FACP) to supervise Form A or B dry contact

devices in a polling circuit

D326A

Americas:

Bosch Security Systems, Inc.

130 Perinton Parkway

Fairport, New York, 14450, USA

Phone: +1 800 289 0096

Fax: +1 585 223 9180

[email protected]

www.boschsecurity.us

Europe, Middle East, Africa:

Bosch Security Systems B.V.

P.O. Box 80002

5600 JB Eindhoven, The Netherlands

Phone: + 31 40 2577 284

Fax: +31 40 2577 330

[email protected]

www.boschsecurity.com

Asia-Pacific:

Robert Bosch (SEA) Pte Ltd, Security Systems

11 Bishan Street 21

Singapore 573943

Phone: +65 6258 5511

Fax: +65 6571 2698

[email protected]

www.boschsecurity.com

Represented by

© Bosch Security Systems Inc. 2010 | Data subject to change without notice

T1372026379 | Cur: en-US, V5, 4 Jul 2010

Reviews: