background image

D263/D273 Series 

| Installation Instructions | 4.0 

Testing 

4.0 Testing 

4.1 Operational 

Testing 

Before and after maintaining or testing the 
fire alarm system, notify all concerned 
parties. 

1.   Apply power to the system and check for alarms. 

a.   Note which detectors are in alarm (if any) and 

remove power to the system. 

b.   Remove the alarmed detectors and recheck for 

proper wiring. 

c.   If the problems persist, replace the affected 

detectors or swap them with known good units. 
This determines if the problem is caused by the 
detector. 

d.   If there is a system alarm with no detector alarms 

present, remove all detectors and check the wiring. 
Pay close attention to the wiring of each EOL 
resistor and EOL module. 

2.   When the system is free of alarms, check each detector 

to ensure the red LED indicator is flashing 
approximately every 3.5 sec. This verifies the detector 
is receiving power and operating properly. 

3.   Test each detector to ensure it causes a control panel 

alarm. Do one of the following to alarm the detectors: 

•  

Place a magnet horizontally against the detector's 
side, centering it over the “T” marked on the head 
activating an internal reed switch. On the D273IS 
this activates the heat detector relay and latches, or 

•  

Use a UL Listed aerosol smoke detector tester 
such as the Home Safeguard Industries’ 25S to 
simulate an alarm. Follow the tester instructions. 
On the D273IS this energizes the smoke detector 
relay and it remains in this state as long as smoke 
is in the chamber (non-latching). 

When a detector alarms, the red LED 
indicator activates and latches ON. 

Clear the alarm by momentarily removing 
power before proceeding to the next 
detector. Clear alarms from each test 
before proceeding to the next detector. 

4.2 Sounder 

Testing 

The sounders on the D263THS, D273ES, D273THES, 
D273THS, and D273THSR produce a steady tone 
(latching) from any alarm condition. The D273IS produces 
a steady tone from a heat alarm (latching) and a temporal 
pattern from a smoke alarm (non-latching). If using a 
D132B, the sounder produces a pattern the same as the 
notification appliance circuit (NAC) control panel. 

4.3 Sensitivity 

Testing 

You must calibrate the detector for continuous operation. 
Depending on local regulations, calibration testing might be 
required more than once a year. NFPA 72 recommends 
calibration testing at installation, and then every other year. 
Perform a Functional Test annually. 

Test the detector’s sensitivity to meet NFPA 72 
requirements by conducting a Magnet Test, or measuring 
the calibration voltage pins with a D1005 Test Cable. You 
can also visually inspect the detector’s LED to quickly 
determine calibration as described in Section 4.3.1 Visual 
Check

The sensitivity tests confirm if the detector is within its 
factory-marked calibration range. 

4.3.1 Visual 

Check 

The D263/D273 Series detectors include the Chamber 
Check

®

 Automatic Trouble Indication allowing the detector 

to automatically indicate when its calibration is out of the 
factory listed range. Use Chamber Check

®

 to meet NFPA 

guidelines for sensitivity testing by visually inspecting the 
detector and checking the flash rate of the LED. 

If the calibration is out of range for more than 24 h, the 
detector’s Alarm LED begins to flash approximately once 
per second. The LED flashes approximately once every 3.5 
sec when the detector is operating normally. 

Perform the visual check on all detectors 
before resetting power. Disconnecting the 
detector power erases this indication. 

If the detector was reset within the last 24 
h or you are unsure of the last reset time, 
perform a Magnet Test or check the voltage 
output to confirm the sensitivity. 

4.3.2 Magnet 

Test 

Hold a magnet horizontally against the detector, centered 
over the "T" for about 10 sec, and observe the LED (refer 
to Figure 1 on page 3). 

•  

If the detector is within the factory marked calibration 
range, it activates an alarm and the Alarm LED latches 
ON. 

•  

If the detector is too sensitive, the LED rapidly flashes 
six times (once every 1/2 sec). Then the detector 
activates an alarm. 

•  

If the detector is not sensitive enough, the LED slowly 
flashes four times, once every 2 sec, and the detector 
activates an alarm. 

•  

If the detector is not operational, it does not activate an 
alarm. Return the unit for repair. 

4.3.3 

Voltage Measurement Test 

1.   Plug a D1005 Test Cable into the calibration voltage 

pins. 

Bosch Security Systems, Inc. | 02/06 | 31341J 

                    Available from A1 Security Cameras 

    www.a1securitycameras.com email: [email protected]

Summary of Contents for D263TH

Page 1: ...D263 D273 Series Installation Instructions Photoelectric Smoke EN Detector Available from A1 Security Cameras www a1securitycameras com email sales a1securitycameras com ...

Page 2: ...g systems refer to NFPA 72 For commercial and industrial installations space the detectors 30 ft 9 2 m apart as recommended by NFPA 72 An LED indicator flashes approximately every 3 5 sec to verify the detector has power and the smoke sampling circuitry is functioning The LED latches ON during an alarm allowing the user to easily verify individual detector alarms After you clear the alarm conditio...

Page 3: ...l injury and damage to the equipment The terminal block is removable It might be easier to remove the terminal block from the detector before making the wire connections Remove the terminal block by pulling it back and then pulling up Refer to Figures 3 through 8 on pages 3 through 5 for wiring details When all wiring connections are made connect the detector to the mounting plate by twisting it c...

Page 4: ...ut Voltage 10 to 30 VDC IN OUT IN OUT 5 6 7 8 Isolated Heat Output IN OUT IN OUT 9 10 Auxiliary Contact Normally Open 11 Black Yellow 24 V or Red 12 V Blue Blue 12 IN OUT IN OUT 1 3 4 1 Last detector 2 Control panel 3 EOL resistor 4 D275 EOL Power Supervision Module Figure 8 D273THR D273THSR Wiring Smoke Power Alarm Loop 1 2 3 4 5 6 7 8 Input Voltage 10 to 30 VDC IN OUT IN OUT Alarm Contacts Norma...

Page 5: ...e the detector for continuous operation Depending on local regulations calibration testing might be required more than once a year NFPA 72 recommends calibration testing at installation and then every other year Perform a Functional Test annually Test the detector s sensitivity to meet NFPA 72 requirements by conducting a Magnet Test or measuring the calibration voltage pins with a D1005 Test Cabl...

Page 6: ...m Before proceeding to the next detector clear each alarm for every test 5 0 Maintenance At least once a year clean the detector Pay particular attention to the screens when cleaning the detector In dusty areas or areas of heavy insect concentration you might need to clean the screens more often Unlatch and pry the cover away from the chassis Refer to Items 1 through 3 in Figure 9 1 Grasp the cham...

Page 7: ...Series Models Model Circuit Type 135 F 57 C Heat Sensor 85 dB Sounder Trouble Relay EOL Relay Auxiliary Relay Current Draw Standby Alarm D263 Two wire 100 µA maximum Determined by control panel D263TH Two wire X 100 µA maximum Determined by control panel D263THC Two wire X X 100 µA maximum Determined by control panel D263THS Two wire X X 100 µA maximum Determined by control panel D273 Four wire 10...

Page 8: ... Perinton Parkway Fairport NY 14450 9199 Customer Service 800 289 0096 Technical Support 888 886 6189 2006 Bosch Security Systems 31341J Available from A1 Security Cameras www a1securitycameras com email sales a1securitycameras com ...

Reviews: