background image

D220ATD Installation Instructions

Page 2

© 2003 Bosch Security Systems

74-07104-000-D

D220ATD

Installation

3.0

Installation

To install the D220ATD Keypad:

1.

Select a mounting location.

Do not locate the D220ATD in areas of extreme cold, such as an uninsulated building, refrigerated areas,
outdoors, or in areas where the temperature can drop below +32°F. Do not mount the keypad in a location
exposed to direct sunlight that makes the display less visible and can also damage keypad components.

Mount the D220ATD on a flat wall or on the following Bosch Security Systems accessories:

D54B Brass Flush Mount Kit

D54C Chrome Flush Mount Kit

D55 Command Center Desk Stand

D56 Command Center Conduit Box

2.

Route the keypad cable to the location where you mount the keypad.

Refer to the panel’s Installation Guide for information on the maximum length of keypad cables and wire
resistance. Be sure to route data wire runs away from electrical, telephone, and other data wiring.

3.

Wire the connector.

The three-wire connector attaches to the keypad cable. Use solder to splice the three-wire connector to the
keypad cable. Be sure to insulate all exposed splices with tape so they do not short to one another.

4.

Remove the front cover from the enclosure base.

Use a small flat-bladed screwdriver to gently push the two bottom cover-tabs back. As you push back the tabs,
lift the bottom of the cover away from the base and then remove the cover.

When using the D220ATD with the D2112/D2112E, cut and remove the R30 resistor. See Figure 2 on
page 3.

If disabling sounder, do so before connecting the keypad to the cable. Disable the sounder by cutting
and removing resistor R22 located in the lower left-hand corner of the board, next to the sounder.
Refer to Figure 2 on page 3.

Fire Points need the trouble sounder. Disable the sounder (by removing R22) stops the D220ATD
from annunciating fire point trouble. If fire points are installed as part of this system, contact the
local AHJ to verify code requirements for fire trouble sounders before disabling the D220ATD
sounder.

Enable sounder for UL systems. For UL installations, the sounder on at least one keypad must
remain connected.

5.

Connect the keypad.

Route the three color-coded flying leads through the opening in the back of the enclosure base and plug into
the serial data wiring connector (J1) in the keypad (see Figure 2).

6.

Mount the enclosure base.

While pushing excess keypad wire back into the wall or gang box, place the enclosure base on the wall in the
desired location. Use a center punch or a pencil to mark the locations of the mounting holes.

If desired, mount the enclosure base to a recessed single-gang wall box. Two mounting screw holes on the base
are positioned for standard single-gang compatibility. Secure the enclosure base to the wall or gang box.

7.

Replace the front cover.

Align the top two tabs of the enclosure cover with the top two tab slots in the enclosure base. Slide the top of
the cover into the base. Gently push the bottom of the cover down on the base until it snaps into place.